4-28
Chapter 4 Wizards Innovation Series Medium Voltage GP Type - G Drives G EH-6385

Drive Commissioning: Exit R eminder

After the Drive Commissioning wizard completes, the drive should have a hard
reset performed. This should clear an y faults that have occurred because of
intermediate parameter values durin g the setup pr ocess.
The following wizards should be run to complete the start-up process:
Cell Test
Motor Control Tuneup
Speed Regulator Tuneup

Drive Commissioning: C onclusion

The Drive Commissioning Wizard has con cluded.
Once this wizard is exited , the drive should have a hard reset per formed. This
should clear any faults that have occurred because of intermediate parameter values
during the setup process.
The following wizards should be run to complete the start-up process:
Cell Test
Motor Control Tuneup
Speed Regulator Tuneup
Line Transfer Tuneup

Line Transfer Tuneup : Overview

The Line Transfer Tuneup wizard is provided to facilitate quick and reliable setup of
line transfer functions. This wizard allows the user to enable tran sfer functions and
direct I/O. If you are using the XferMtr command it will check phase rotation, and
measure the phase angle and voltage magnitude relationships needed to correctly
carryout the command. Because the wizard uses drive outpu t instrumentation to do
these measurements it will generally be necessar y for the user to manually close the
utility contactor to connect the dr ive output to the line. Depending on the application
it may be necessary to disconnect the motor in order to complete the wizard. Until
this wizard has be successfully completed the drive will not accept line transfer
commands.
There are many issues beyond drive software that must be consi dered before
attempting trans fers and captures. For detailed in formation all applications issues see
the "Innovation Seri es Line Transfer Application Guide".

Line Transfer Tuneup : Motor Transfer Data

This wizard can configu re the drive to perform motor tran sfer and capture
operations. The motor tr ansfer data parameters confi gure the drive to transfer a
motor to the utility line. Enter the motor transfer data parameters.
Transfer mtr req sel selects the signal that initiates the motor transfer . Set as
required by your application.