GEH-6385 Reference and Troubleshooting, 2300 V Drives Chapter 3 Paramters/Functions
3-103
The active generating torque limit is subject to further limiting by the DC Bus
Regeneration Control. The Regeneration Control can be configured to limit
regenerative capa bility in response to DC Bus Voltag e exceeding programmed
limits. Both motoring & generating torque limits ar e dynamically applied as positive
& negative torque limits according to the detected quadrant of operation.
The magnitude current limit is affected as a limit to the torque-producing current
component based upon a dynamic calculation that considers the active value of the
flux-producing current component. Pullout protection limits and power-dip clamp
controls may dyn amically further decrease the current limit prior to application to the
torque-producing current command.
Appropriate excitation of the induction motor is provided by the motor control
algorithm accordin g to configured motor nameplate d ata and prevailing power
supply conditions. However, in some advanced applications it may be appropriate for
the application con trol layer to define further modification to the flux reference. This
is accomplished using the Flux ref ratio signal, which may be adjusted statically by
the fixed parameter Flux ref ratio setpt or a dynamic signal selected by the parameter
Flux ref ratio sel. In either case the signal is defined a s a per-unit offset to the
nominal flux reference defined by the motor control; one per-unit flux is defined as
Motor rated voltage at Motor rated freq.
Related diagrams
Motor Control Interface (Core)
Speed Control Fault C heck
The Speed Control Fault Check checks for the following fault an d alarm conditions:
Over speed
Failure to rotate
Loss of spd control
Reverse rotation

Over speed configuration and operation

The following parameter configures the Over speed fault.
Parameter Description
Over speed flt level Overspeed fault level. RPM
The Over speed fault is declared when the following condition is met.
ABS(Speed reg fbk) > Over speed flt level