3-64
Chapter 3 Paramters/Functions Innovation Series Medium Voltage GP Type - G Drives GEH-6385
The capability of the drive to produce the overload current depends on the capacity
of its power circuit. Especially at higher overload levels, the drive may not be able to
sustain the motor's overload current as defined by Motor protect class.
The motor heating model has the capability of implementing a speed dependent
motor cooling characteristic. The user defined cooling characteristic is activated
when Disable TOC profile is False. At present, the cooling characteristic
functionality is not fully supported. Disable TOC profile shou ld not be changed fr om
its default value of True with out factory assist ance.