Chapter 3 Paramters/Functions Innovation Series Medium Voltage GP Type - G Drives GEH-6385
Diagnostic and Utility Functions

Diagnostic and Utility Overview

The Innovation Series products contain a number of diagnostic functions. More
information is available for the following topics.
Capture Buffer
General Purpose Constants
General Purpose Filters
Oscillator
Position Feedback
Predefined Constant s
Signal Level D etector (SLD)
Simulator

Capture Buffer

The Innovation Series ca pture buffer is used to collect coh erent data at a specified
rate in the drive. The capt ure buffer is circular, and will col lect a fixed number of
samples of each data chann el before overwriting the oldes t data. The capture buffer
can be triggered on any avai lable variable signal in the dri ve by using a Boolean
trigger mode or comparison to a value. The capture buffer will also trigger on a Tr ip
fault. It is u seful for capturi ng drive variabl es for troublesh ooting field pr oblems and
capturing specific dr ive events. The Trend Recorder can display the capture buffer
output.
Function Inputs
The following table specifies the input parameters to the Capture Buffer functi on.
Parameter Description
Capture ch1 select Selects capture buffer channel #1 variable.
Capture ch2 select Selects capture buffer channel #2 variable.
Capture ch3 select Selects capture buffer channel #3 variable.
Channels 3 & 4 are active when Capture buff
config is set to either 4 channels enabled or 8
channels enabled.
Capture ch4 select Selects capture buffer channel #4 variable.
Capture ch5 select Selects capture buffer channel #5 variable.
Channels 5, 6, 7, & 8 are active when Capture
buff config is set to 8 channels enabled.
Capture ch6 select Selects capture buffer channel #6 variable.
Capture ch7 select Selects capture buffer channel #7 variable.
Capture ch8 select Selects capture buffer channel #8 variable.