GE Medium Voltage GP Type G Drives, 2300 V manual Diagnostic variables, Connection ok indications

Models: Medium Voltage GP Type G Drives 2300 V

1 266
Download 266 pages 45.22 Kb
Page 91
Image 91

Diagnostic variables

The following table specifies variables that indicate the LAN health and status for the LAN Configuration and Health function.

Variable

Description

LAN connection ok

Indicates that the health of the LAN connection is

 

good, such that the LAN watchdog function is

 

satisfied.

LAN commands OK

Indicates that the health of the LAN references is

 

good, based upon detection of two successive LAN

 

connection ok indications.

Heartbeat ref, lan

LAN heartbeat signal that proceeds from the

 

application layer to the local device, used locally for

 

LAN heartbeat trip) and LAN heartbeat alarm)

 

detection, and as the source of the reflected

 

Heartbeat fbk, lan signal.

Heartbeat fbk, lan

Local device reflection of the Heartbeat ref, lan

 

signal that is sent back to the application layer.

Sys ISBus error cnt

Counter signal which provides an indication of the

 

rate of occurrence of ISBus fault conditions.

Sys ISBus error reg

Bit-coded value of the last ISBus fault detected;

 

each bit indicates a particular ISBus fault seen by

 

the control.

Frame PLL OK status

Boolean signal indicating the lock status of the

 

Frame Phaselock Loop.

FPLL Phase error

Phase error signal for the Frame Phaselock Loop.

 

Scaling is per-unitized such that unity corresponds

 

to the full frame period; signal values range from

 

minus one-half to plus one-half.

FPLL Freq Output

Frequency adjustment output signal for the Frame

 

Phaselock Loop. Scaling is per-unitized such that

 

unity corresponds to the full frame period; signal

 

values range from minus output limit to plus output

 

limit.

 

 

Function description

Determining the integrity of the LAN interface involves several communication layers, and may vary depending upon the specific communication options in use. The Innovation Series Drive has two levels of validation available: LAN watchdog and LAN heartbeat. Status information is conveyed to the user and/or application by status signals and fault declarations.

GEH-6385 Reference and Troubleshooting, 2300 V Drives

Chapter 3 Paramters/Functions 3-37

Page 91