GE 2300 V manual AC line frequency is marginally excessive, Frequency was at 50hz

Models: Medium Voltage GP Type G Drives 2300 V

1 266
Download 266 pages 45.22 Kb
Page 34
Image 34

No.

Name

Type

Description

91

AC line freq high

Alarm

The AC line freq high alarm occurs when the control firmware detects that the

 

 

 

frequency of the AC line is above the value of Over freq alm level, which has

 

 

 

a suggested value of nominal frequency plus 17.3 rad/sec.

 

 

 

The frequency value used for this comparison is a low-pass filtered version of

 

 

 

the fastest version. The filter is set to .2 rad/sec as a default, so transient

 

 

 

over-frequency values are allowed above the threshold value without causing

 

 

 

this alarm.

 

 

 

This alarm will cease once the filtered value of filtered frequency has

 

 

 

decreased to below the value of Over freq alm clear, which has a suggested

 

 

 

value of nominal frequency plus 15.7rad/sec.

 

 

 

Primary causes:

 

 

 

AC line frequency is marginally excessive.

 

 

 

Possible configuration faults:

 

 

 

Source has been applied 60hz while the factory setup value, AC grid

 

 

 

frequency was at 50hz.

 

 

 

Possible board failures:

 

 

 

VATF-SRC

 

 

 

FOSA

 

 

 

BICM

 

 

 

DSPX

 

 

 

 

92

AC line under freq

Trip

The AC line under freq trip fault occurs when the control firmware detects that

 

 

 

the frequency of the AC line is below the value of Under freq flt level, which

 

 

 

has a suggested value of nominal of 50% of nominal.

 

 

 

The frequency value used for this comparison is a low-pass filtered version of

the fastest version. The filter is set to .2 rad/sec as a default, so transient under-frequency values are allowed below the threshold value without causing this trip fault.

Primary causes:

AC line frequency is low.

Possible configuration faults:

Source has been applied at 50hz while the factory setup value, AC grid frequency was at 60hz.

Possible board failures:

VATF-SRC

FOSA

BICM

DSPX

2-18 Chapter 2 Faults and Troubleshooting Innovation Series Medium Voltage GP Type - G Drives GEH-6385

Page 34
Image 34
GE 2300 V, Medium Voltage GP Type G Drives manual AC line frequency is marginally excessive, Frequency was at 50hz