3. Operation
( ○ indicates the display is OFF)
( ● indicates the display is ON)
4. Displays and beeps when there is an equipment failure (continued) ( indicates blinking)
No. | Status | Power supply | Bypass | Battery | Beep | Charging | Description | Solution |
indicator | output | operation | replacement | |||||
| lamp | lamp | lamp |
|
|
|
| |
|
|
|
|
|
| |||
|
| ○ | ○ | ○ |
| ON | Output stopped due to output | Check that the AC input of |
13 |
| Continuous | connected devices is not | |||||
| or | |||||||
|
|
|
|
|
| discharging |
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Replace the external cooling fan. |
|
|
|
|
|
| ON | Moved to bypass operation due | See also “Replacing the fan” Page 62 |
14 |
| ● | ● | ○ | Continuous | to problem with the external | ||
| The fan can be replaced via the | |||||||
| or | cooling fan (Note 1). | ||||||
|
|
|
|
|
| discharging | rear panel without stopping this unit. | |
|
|
|
|
|
|
|
| Use replacement fan sold separately. |
|
|
|
|
|
|
|
| (Note 2) |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Turn OFF this unit and all connected |
|
|
|
|
|
|
| Failure occurred. When the beep | devices. Then, turn the power switch |
|
|
|
| ○ |
|
| back ON for this unit only. If the display | |
15 |
| ―― | ―― | Continuous | ―― | stop switch is pressed, the details | does not change, there is a problem | |
|
| (Note 3) | (Note 3) |
|
|
| of the error are displayed | with this unit. Contact the shop of |
|
|
|
|
| (Nos. 16 to 23). | |||
|
|
|
|
|
|
| purchase or our peripheral device | |
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
| customer support center at: _____ |
|
|
|
|
|
|
|
|
|
|
| ● | ● | ○ |
|
| Moved to bypass operation due | Displays the details of the error that |
16 |
| Continuous | ―― | to output voltage error (over) | occurred only while pressing the beep | |||
|
|
|
|
|
|
| (Note 1). | stop switch while in state No. 15. |
|
|
|
|
|
|
|
|
|
|
| ● | ● | ○ |
|
| Moved to bypass operation due |
|
17 |
| Continuous | ―― | to output voltage error (under) | (Same as above.) | |||
|
|
|
|
|
|
| (Note 1). |
|
|
| ● | ○ | ○ |
|
| Moved to Battery Mode due to |
|
18 |
| Continuous | ―― | battery charge voltage error (over). | (Same as above.) | |||
|
|
|
|
|
|
| Output will stop when the battery is dead. |
|
|
| ○ | ○ | ○ |
|
| Output stopped because the |
|
19 |
| Continuous | ―― | output of the battery charge | (Same as above.) | |||
|
|
|
|
|
|
| voltage |
|
|
| ● | ● | ○ |
|
| Moved to bypass operation due |
|
20 |
| Continuous | ―― | to problem with the internal | (Same as above.) | |||
|
|
|
|
|
|
| temperature (Note 1). |
|
|
| ● | ● | ○ |
|
| Moved to bypass operation due |
|
21 |
| Continuous | ―― | to bypass bus voltage error | (Same as above.) | |||
|
|
|
|
|
|
| (Note 1). |
|
|
| ―― | ―― | ○ |
|
| (1) Output stopped due to |
|
22 |
| Continuous | ―― | system error. | (Same as above.) | |||
| (Note 3) | (Note 3) | ||||||
|
|
|
|
|
|
| (2) Other error occurred. |
|
Note 1: In bypass operation, commercial power is output directly. Output stops when a power failure (AC input OFF) occurs in bypass operation.
Note 2: Fan replacement performed by the user does not comply with UL, CE standards.
Note 3: The displays and operations vary according to the status.
5. Display and beep for battery replacement
|
|
|
|
|
|
|
|
|
|
| ● | ○ |
| Intermittent |
| The battery test detected | |
23 |
|
| ON | a weak battery | ||||
|
|
|
|
| intervals |
| (warning only, output continues). | |
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
Replace the battery.
You can replace the weak battery with a separately purchased replacement battery as needed.
40