7.Using the UPS monitoring software and contact signal
●Remote ON/OFF Signal
Remote ON/OFF signals can be used to start and stop the UPS, by using either an externally connected con- tact or the ON/OFF status of the open collector circuit. To use this function, turn on the Power Switch of the UPS. (Note: When there is no AC power supply, it is not pos- sible to start up UPS by the remote ON/OFF signals even though cold start is set ON.)
Connection terminals are at contact signal connector pins 6 ,7 and the remote ON/OFF connector.
3. Items that can be set using the contact signal card
Please make a cable to connect to the system by yourself.
External contact | Operate |
Open | Start |
|
|
Close | Stop |
|
|
See also "8. Example of the use of the Contact Signal circuit" ➛ Page 81
Jumper settings (8 digits)
DIP switches (3 digits)
■Setting the switches
Caution
After changing the setting switch, disconnect the AC input plug, wait until the status indicator is completely OFF, and then reinsert the AC input plug.
●The setting switch changes do not become valid until the AC input plug is reinserted.
By using the switches of contact signal card, set the item below.
78