Omron BU1002SW, BU3002SW Interpreting beeps and displays, Displays and beeps in normal operation

Models: BU3002SW BU1002SW

1 93
Download 93 pages 54.62 Kb
Page 41
Image 41
3-3 Interpreting beeps and displays

3. Operation

3-3 Interpreting beeps and displays

 

 

 

 

 

 

 

 

 

( indicates the display is OFF)

 

1. Displays and beeps in normal operation

 

( indicates the display is ON)

 

 

( indicates blinking)

 

No.

Status

Power supply

Bypass

Battery

Beep

Charging

Description

Solution

 

indicator

output

operation

replacement

 

 

 

lamp

lamp

lamp

 

 

 

 

 

 

 

 

 

 

 

 

 

1

 

None

OFF

No AC input.

--

 

 

Operation stopped.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2

 

None

ON

There is AC input.

--

 

 

Power switch is OFF.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3

 

None

ON

Power switch is ON.

--

 

 

Operating normally.

 

 

 

 

 

 

 

 

 

 

 

2. Displays and beeps while testing

4

5

None

OFF

Self-diagnostic test in progress.

--

Discharging

None

OFF

Auto battery test in progress.

--

Discharging

 

 

 

 

 

 

 

3. Displays and beeps during power failure or AC input error

 

 

 

 

 

Intermittent

 

In Battery Mode due to power

Perform shutdown operations

6

 

 

 

OFF

failure or AC input error.

 

 

 

4-second

for the connected devices

 

 

 

Discharging

Output will stop if Battery

 

 

 

 

intervals

and stop them.

 

 

 

 

 

 

Mode continues.

7

 

 

 

Intermittent

OFF

(Same as above.)

 

 

 

 

1-second

Discharging

Battery level is low, so output

(Same as above.)

 

 

 

 

intervals

 

will soon stop.

 

 

 

 

 

 

OFF

Battery is dead,

 

8

 

 

 

None

so output stopped.

Charge the battery.

 

 

 

Discharging

(This is displayed only for

 

 

 

 

 

 

 

 

 

 

 

a few seconds.)

 

 

 

 

 

 

 

AC input voltage is too high

Use within the AC input voltage/

 

 

 

 

 

 

(over).

9

None

(ON)

 

frequency range described

 

in the specifications.

 

 

 

 

 

 

AC input frequency is too high

→ See Page 88

 

 

 

 

 

 

 

 

 

 

 

 

 

(over).

 

 

 

 

 

 

 

AC input voltage is too low

 

 

 

 

 

 

 

(under).

 

10

None

(ON)

 

(Same as above.)

 

 

 

 

 

 

AC input frequency is too low

 

 

 

 

 

 

 

(under).

 

4. Displays and beeps when there is an equipment failure

11

12

 

 

 

 

 

There are too many connected

 

 

 

 

 

 

devices and the rated capacity is

 

 

 

 

 

 

exceeded. If this state continues

 

 

 

 

 

 

for as long as or longer than the

 

 

 

 

 

 

times described below,

 

 

 

 

 

 

commercial power continues

 

 

 

 

Intermittent

 

to be supplied through bypass

 

ON

operation (Note 1).

Reduce the number of connected

0.5-second

or

When connection capacity is

devices until the display appears

 

 

 

intervals

discharging

at 100% or higher: Bypass

 

 

 

as in status No. 3.

 

 

 

 

 

operation begins after 10 seconds

 

 

 

 

 

When connection capacity is

 

 

 

 

 

 

at 120% or higher: Output stops

 

 

 

 

 

 

after 1 minute (Go to No.12)

 

 

 

 

 

 

When connection capacity is

 

 

 

 

 

 

at 140% or higher: Output stops

 

 

 

 

 

 

after 10 seconds (Go to No.12)

 

 

 

 

 

 

 

Turn OFF the power switches of

 

ON

Output stopped due to exceeded

all devices connected to the unit,

Continuous

or

reduce the number of connected

discharging

connection capacity.

devices, and turn the power switch

 

 

 

 

 

 

back ON again.

 

 

 

 

 

 

 