Omron BU3002SW, BU1002SW Connecting the equipment, Group control of power supply output

Models: BU3002SW BU1002SW

1 93
Download 93 pages 54.62 Kb
Page 26
Image 26
2-3 Connecting the equipment

2. Installation and connection

2-3 Connecting the equipment

●Group control of power supply output Caution

Do not connect devices with rated voltage of 200 to 240 VAC or higher.

The rated output voltage of this device is 200 to 240 VAC.

Overcurrent may damage the connected devices.

When in use, make sure the output terminal block cover is attached. Do not turn ON the power switch when it is detached.

Voltage is applied to the output terminal block when the power switch is ON, which can result in electric shock.

<Example of connection 1 >

BU1002SW

PC

To power supply output receptacle

BU3002SW

PC

To power supply output receptacle

<Example of connection 2 >

Connected device (1)

Connected device (2)

To the terminal block for output

Connected device (1)

Connected device (2)

To the terminal block for output

Group control of power supply output

This function can be used with the UPS monitoring software included with the UPS. The output receptacles of the BU1002SW are separated into 3 groups: A, B, and C.

1.Power supply output group A

Output begins at the same time as startup.

2.Power supply output group B, C

The output start times for power supply output group B and C are independent of power supply output group A, so they can be delayed or set to precede the output stop time.

The output start/stop time control funtion is available when using the included “PowerAct Pro” UPS monitoring software, “UPS Power Manager” or “SNMP/Web card”.

Output ON/OFF can be controlled with the included UPS monitoring software while the BU1002SW is operating.

The delay settings and ON/OFF control described here can be performed independently for power

supply output group B and power supply output group C.

This function can be used to set the startup order of servers, peripheral devices, etc. The output receptacles can also be forcibly turned ON/OFF remotely.

24

Page 26
Image 26
Omron BU3002SW, BU1002SW Connecting the equipment, Do not connect devices with rated voltage of 200 to 240 VAC or higher