Omron BU1002SW Stopping the UPS, Recycling and Discarding the Battery, Check Check Click

Models: BU3002SW BU1002SW

1 93
Download 93 pages 54.62 Kb
Page 75
Image 75
 Check

7Using the UPS monitoring software and contact signal

4)In the "UPS signal polarity" box, click on the boxes to the right of "Power supply failure/battery drive (P)" and "Low battery (L)" signals to insert check marks.

Set the polarity for each signal to "Negative". Click the "End" button.

Stopping the UPS Check

Recycling and Discarding the Battery Check Manual background Click

5)Click the "OK" button in the "Power supply options" window. Setup is complete.

Manual background Click

Manual background Click

When a power failure occurs, Windows shutdown starts once the Low battery level signal is detected.

If the power is restored before the Low battery level signal is detected, Windows shutdown does not start and the normal monitoring state is restored.

Stopping the UPS

Recycling and Discarding the Battery

In the Windows Server 2003/XP/2000 UPS service, there is no function to stop the UPS. After Win- dows is shut down, manually turn OFF the unit's power switch.

73

Page 75
Image 75
Omron BU1002SW, BU3002SW Stopping the UPS, Recycling and Discarding the Battery, Check Check Click, Click Click