4. UPS functions

Setting switch function list

No.

Function to set

OFF side

ON side

 

 

 

 

1

Setting for beeper sound in the

Beeper sounds

Beeper does

 

event of power failure, etc.

not sound

2

Auto startup setting after

Perform auto startup

Do not perform

 

recovery from power failure

auto startup

 

 

 

 

3

Setting for whether or not to

Perform test

Do not perform

 

perform battery test

test

 

 

 

 

 

 

4

Auto startup mode setting

Mode A

Mode B

 

 

 

 

5

---

---

---

6

---

---

---

 

 

 

 

7

BS signal valid range setting

Always valid

Valid only during

 

Battery Mode

 

 

 

 

8

---

---

---

 

 

 

 

*In the factory settings, everything is OFF.

Setting for beeper sound in the event of power failure, etc. (setting switch 1 )

Factory setting: OFF

ON

 

 

 

 

 

 

 

 

 

DIP

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1 2 3 4 5 6 7 8

OFF: The beeper sounds when an alarm is necessary.

ON: The beeper does not sound for backup operation or battery replacement. The beeper sounds for other errors (connection capacity exceeded, operation error, etc.).

Auto startup setting after recovery from power failure (setting switch 2 )

Factory setting: OFF

ONDIP

1 2 3 4 5 6 7 8

OFF: Automatically starts when power is restored.

After a power failure occurs and the unit shuts down using the shutdown software or contact signal(BS signal), the unit automatically starts and begins to output when the commercial power is restored.

ON: Does not automatically start when power is restored.

After the unit is shut down with the UPS monitoring software or contact signal (BS signal), it does not start up when commercial power is restored. Startup is performed by turning the power switch OFF once, and then back ON again.

43

Page 45
Image 45
Omron BU1002SW, BU3002SW specifications Setting switch function list