4. UPS functions
Setting switch function list
No. | Function to set | OFF side | ON side |
|
|
|
|
1 | Setting for beeper sound in the | Beeper sounds | Beeper does |
| event of power failure, etc. | not sound | |
2 | Auto startup setting after | Perform auto startup | Do not perform |
| recovery from power failure | auto startup | |
|
|
|
|
3 | Setting for whether or not to | Perform test | Do not perform |
| perform battery test | test | |
|
| ||
|
|
|
|
4 | Auto startup mode setting | Mode A | Mode B |
|
|
|
|
5 | |||
6 | |||
|
|
|
|
7 | BS signal valid range setting | Always valid | Valid only during |
| Battery Mode | ||
|
|
|
|
8 | |||
|
|
|
|
*In the factory settings, everything is OFF.
●Setting for beeper sound in the event of power failure, etc. (setting switch 1 )
…Factory setting: OFF
ON |
|
|
|
|
|
|
|
|
| DIP | ||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
1 2 3 4 5 6 7 8
OFF: The beeper sounds when an alarm is necessary.
ON: The beeper does not sound for backup operation or battery replacement. The beeper sounds for other errors (connection capacity exceeded, operation error, etc.).
●Auto startup setting after recovery from power failure (setting switch 2 )
…Factory setting: OFF
ONDIP
1 2 3 4 5 6 7 8
OFF: Automatically starts when power is restored.
After a power failure occurs and the unit shuts down using the shutdown software or contact signal(BS signal), the unit automatically starts and begins to output when the commercial power is restored.
ON: Does not automatically start when power is restored.
After the unit is shut down with the UPS monitoring software or contact signal (BS signal), it does not start up when commercial power is restored. Startup is performed by turning the power switch OFF once, and then back ON again.
43