Omron BU3002SW, BU1002SW specifications References, A. Specifications

Models: BU3002SW BU1002SW

1 93
Download 93 pages 54.62 Kb
Page 90
Image 90
References

Reference

References

A. Specifications

Type

 

BU1002SW

BU3002SW

Method

Operation method

Full-time inverter supply method

 

Connectable devices

PC, display, and peripherals

Input

Rated input voltage

200 to 240V ± 10%

 

Allowable voltage range

AC145±4 to 276±4V (with 85% or less connection load)

 

 

AC170±4 to 276±4V (with 85% or more connection load)

 

Frequency

50/60Hz ± 4Hz

 

Maximum current

7.4A

16A

 

Phase

Single-phase, two-wire

 

Input plug shape

NEMAL6-15P

NEMAL6-20P

 

Input protection

Reset-type overcurrent protection device

 

Input protection capacity

10A

20A

Output

Allowable connection capacity *1

1000VA/700W

3000VA/2100W

 

Voltage (effective value) *2

200V mode

AC200V ± 3%

 

 

220V mode

AC220V ± 3%

 

 

230V mode

AC230V ± 3%

 

 

240V mode

AC240V ± 3%

 

Peak voltage value

200V mode: AC282V ± 6% 220V mode: AC310V ± 6%

 

(In Commercial Power Mode)

230V modeAC324V±6% 240V modeAC338V±6%

 

Peak voltage value

200V modeAC282V±6%

220V modeAC310V+6%/-10%

 

(In Battery Mode)

230V modeAC324V+6%/-10% 240V modeAC338V+6%/-12%

 

Frequency

50/60Hz ± 1Hz

 

Phase

Single-phase, two-wire

 

Output waveform

Sine wave

 

Waveform distortion rate

200V mode: 6% max.

220V mode: 10% max.

 

(Rectified load, at rated output)

230V mode: 10% max.

240V mode: 12% max.

 

Number of output receptacles

IEC60320 C13 : 3 pcs.

IEC60320 C19 : 1 pcs. C13 : 5 pcs.

 

 

Terminal block: 2 lines

Terminal block: 2 lines

 

Power failure switching time

Uninterrupted

 

Commercial direct shipment (switching time)

4msec. max.

 

Backup time *3

Minimum 5 minutes

Battery

Type

Compact sealed lead battery

 

Sealed lead battery life expectancy

4 to 5 years (long operating life) *At ambient temperature of 20°C

 

Battery capacity (V/Ah) (x Quantity)

12V DC/ 7.2 Ah (x 3)

12V DC/ 9 Ah (x 6)

 

Charging time

8 hours *4

Environment

Operating ambient temperature

0 to 40°C (during operation)/ -15 to 50°C (during storage)

 

Operating ambient humidity

25 to 85%RH (during use)/10 to 90%RH (during storage)

Dimensions

 

145 x 395 x 224 (±1) mm *5

213 x 537 x 432 (±1) mm *6

Weight of unit

 

Approx. 15.5 kg

Approx. 35 kg

Internal power

 

50W (100W max.)

55W (155W max.) *7

consumption (max.)

 

 

 

 

Noise regulation

 

VCCI Class A

(compliance standard)

 

 

 

 

Safety standard compliance

 

UL/CE

Noise

 

50 dB max.

55 dB max.

*1: Make sure that both the VA value and the W value of the load capacity connected to the UPS are within the range specified here.

*2: Check the operation beforehand if the unit is used in any mode other than “200V AC mode”. In some cases, the maximum voltage of output in Battery Mode may be lower than the maximum voltage in usual operation (commercial power supply).

*3: The backup times shown here are for when rated load is connected, at 20°C, and for initial characteristics.

*4: When an additional battery unit is connected, the charging time is 24 hours.

*5: The height includes the 13-mm height of the rubber feet.

*6: The height includes the 56mm height of the casters.

*7: 170W max when and additional battery unit is connected.