6.Maintenance and inspection

7.Attach the front panel.

Insert the lug at the bottom of the front panel into the hole in the main body and push it towards the main body.

Use a screwdriver to securely tighten (clockwise) the 2 screws at the top of the front panel.

90% 50% 30%

2 1

Tighten the 2 screws.

90% 50% 30%

3

Battery replacement is now complete.

Procedure for recycling the battery

<BU3002SW>

1. Use a screwdriver to loosen (anti-clockwise rotation) the 4screws on the front panel of the unit, until they turn freely. (The screws cannot be removed from the front panel.)

Pull the front panel towards you to remove it.

Loosen the 4 screws.

1

2. Remove the battery connectors from the lower plate cover and disconnect each of the connectors.

Battery connector

1

Disconnect by holding here.

Plate cover

2

1

58

Page 60
Image 60
Omron BU3002SW, BU1002SW specifications Battery replacement is now complete