Manuals
/
Omron
/
Computer Equipment
/
Power Supply
Omron
BU3002SW, BU1002SW specifications Side view, Air inlet
Models:
BU3002SW
BU1002SW
1
16
93
93
Download
93 pages
54.62 Kb
13
14
15
16
17
18
19
20
<
>
Troubleshooting
Specs
Install
C. Circuit block diagram
Perform replacement on a stable and flat place
Dimension
Maintenance
Connecting the equipment
Perform UPS service setup
Procedure for connection to BU1002SW output terminal block
Page 16
Image 16
1. Preparation
Side view
<BU1002SW>
Front side
Rear side
Air inlet
<BU3002SW>
Front side
Rear side
14
Page 15
Page 17
Page 16
Image 16
Page 15
Page 17
Contents
BU1002SW/BU3002SW
Uninterruptible Power Supply UPS/200 to 240V specifications
Instruction Manual
Features of this product
Notes on the use of the Backup Power Supply
Introduction
Disclaimers
IMPORTANT SAFETY INSTRUCTION 1.SAVE THESE INSTRUCTIONS
2.SYMBOL
3.INTERNAL BATTERY
4.TEMPERATURE RATING
Procedure from installation to operation
Start Installation/connection
Maintenance
Preparation for operation
Table of Contents
Table of Contents
7. Using the UPS monitoring software and contact signal
Safety precautions
Keep plastic package bags out of reach of children
Do not install the unit in other than specified orientations
Do not use the unit where the maximum temperature exceeds 40C
Do not install or store the unit in the places listed below
Provide secure grounding
Do not connect devices with rated voltage of 200 to 240 VAC or higher
Do not use the unit in a closed place and do not cover the unit
Do not allow the unit to come in contact with water
If fluid leaks from the unit, do not touch the fluid
Do not insert metal objects into the battery connectors
Perform replacement on a stable and flat place
Use a specified battery for replacement
Do not replace the battery in a place where there is flammable gas
Do not use a new battery and an old battery at the same time
Do not put the battery into fire and do not break it
Caution for battery replacement
Do not connect a page printer such as a laser printer to the unit
Charge the battery for at least 8 hours soon after purchasing the unit
Do not perform a withstand voltage test
Explanation
Quitting Battery Mode
Rebooting
Scheduled operation using the UPS monitoring software
1-2Checking the contents
1. Preparation
1-1 Unpacking the product
1 Accessories related to the main unit
1-3 Name of each part
Front view
Side view
Air inlet
Rear view
1-4 Explanation of symbols used on unit
Description
2. Installation and connection
2-1 Precautions and notes on installation and connection
Keep plastic package bags out of reach of children
Provide secure grounding
Do not install the unit in other than specified orientations
Do not use the unit where the maximum temperature exceeds 40C
Do not install or store the unit in the places listed below
Caution for installation and connection
Do not connect devices with rated voltage of 200 to 240 VAC or higher
Do not connect a page printer such as a laser printer to the unit
Do not perform a withstand voltage test
2-2 Installation and connection
Correct Positions
Incorrect Positions
Be careful not to get your fingers caught when arranging the unit
Be careful not to get your fingers caught when arranging the unit
Caster at the bottom may be removed when sitting horizontally
Correct Positions
Incorrect Positions
2. Installation and connection Installing the BU3002SW vertically
Group control of power supply output
2-3 Connecting the equipment
Do not connect devices with rated voltage of 200 to 240 VAC or higher
2-3-1 Connecting a device to the power supply output BU1002SW
BU1002SW Rated value of output capacity Max. 1kVA/700W
Procedure for connection to BU1002SW output terminal block
emergency stop switch ESD
200 to 240 VAC 3P receptacle
Connect the ground wire to the Grounding terminal
PC Grounding terminal
2-3-2 Connecting a device to the power supply output BU3002SW
BU3002SW Rated value of output capacity Max. 3kVA/2100W
Procedure for connection to BU3002SW output terminal block
switch ESD
N E L
Connect the ground wire to the Grounding terminal
PC 200 to 240 VAC 3P receptacle Grounding terminal
1 Turn ON the units power switch
2-4 Checking the operation
2 Bring all the connected devices into operation
5 In Battery Mode, check the units LED display and beep sound
6 Connect the AC input plug to a wall outlet commercial power again
2-6 Measuring the initial value of backup time
2-5 Charging the battery
2-7 Recharging the battery
3-1 Precautions and notes for operation
3. Operation
Do not allow the unit to come in contact with water
Do not use the unit in a closed place and do not cover the unit
Quitting Battery Mode
Rebooting
Scheduled operation using the UPS monitoring software
Explanation
Start procedure
3-2 Start and stop procedures and basic operation
Operation Turn on the power switch of the UPS
indicator replacement
Operation after a power failure
See also
Operation during recovery from a power failure
Stop procedure
Connection capacity/battery level meter
Operation Turn ON the power switch of the UPS
3-3 Interpreting beeps and displays
2. Displays and beeps while testing
3. Displays and beeps during power failure or AC input error
4. Displays and beeps when there is an equipment failure
5. Display and beep for battery replacement
4-1 Suspending a beep
4. UPS functions
4-2 Self-diagnosis test
4-4 Changing the setting of the functions
4-3 Description of the auto battery test function
1. Selecting functions with the DIP switch
… Factory setting OFF
Auto startup setting after recovery from power failure setting switch
… Factory setting OFF
Setting switch function list
… Factory setting OFF
Setting for whether or not to perform battery test setting switch
Auto startup mode setting setting switch 4 … Factory setting OFF
4. UPS functions
BS signal valid range setting setting switch 7 … Factory setting OFF
BS signal valid range setting setting switch
The settings available for this operation are shown below
2. UPS operation mode settings
2-1 Settable items and explanations
4. UPS functions 4 Signal input/output test BL/TR/BU/WB/BS/remote
Four types of output signal can be forcibly turned ON
Cold start ON/OFF setting Output voltage setting
2-2 Settings
Power supply output stop delay time setting Signal input/output test
Turn ON the power switch while the beep stop/test switch is pressed
C Press and hold the beep stop/test switch for more than 3 seconds
Cold start OFF mode Factory-shipped setting
0.2 minute delay
5. Measuring the backup time
5-1 How to measure backup time
5-2 Estimated backup time
For Windows Server 2003/XP/Me/2000/Windows NT/Linux/Mac
Page
6. Maintenance and Inspection
6-1 Checking the battery
Do not insert metal objects into the battery connectors
1. Life of battery estimated replacement timing
6-2 Replacing the battery
Perform replacement on a stable and flat place
Use a specified battery for replacement
Do not replace the battery in a place where there is flammable gas
Do not put the battery into fire and do not break it
Do not use a new battery and an old battery at the same time
Battery recycling
Procedure for recycling the battery
Do not hold the connector or cable of the battery pack
Red tape Battery connector
Battery pack Pullout label Pull this to remove
Remove the 2 screws
Insert the connector again
6. Maintenance and inspection 7. Attach the front panel
Procedure for recycling the battery
BU3002SW
Do not hold the connector or cable of the battery pack
Battery pack
Insert the connector again
After replacing the battery when operation was stopped
After replacing the battery during operation
Tighten the 4 screws
6-3 Replacing the fan
Precautions when replacing the fan
Do not insert your hand or metal objects into the fan recess
Do not put your fingers into the fan
Fan replacement procedure
6-4 Cleaning
1. Cleaning the UPS
7.Using the UPS monitoring software and contact signal
7. Using the UPS monitoring software and contact signal
UPS monitoring software
UPS monitoring software function list
7.Using the UPS monitoring software and contact signal
Software
When using PowerAct Pro “UPS monitoring software for Windows/Linux”
PowerAct Pro UPS monitoring software
1. Connect the UPS to a computer
RS-232C
2. Install the included UPS monitoring software on each computers
When using UPS Power Manager “UPS monitoring software for Mac”
2. Install the included UPS monitoring software on the computer
7.Using the UPS monitoring software and contact signal
Scheduled operation using the UPS monitoring software
Explanation
2. Install the included UPS service driver on the computer
1. Connect the UPS to a computer
RS-232C
The RS232C cable and USB cable cannot be used at the same time
7.Using the UPS monitoring software and contact signal
Connect to contact signal connector on UPS
1. Connect the UPS to a computer
BU1002SW
2. Perform UPS service setup
When using the Windows Server 2003/XP/2000 standard UPS service
Click Click
Click Click Click Click
Stopping the UPS
Recycling and Discarding the Battery
Check Check Click
Click Click
How to set up UPS service set the time to shut down Windows
Click
Check
Click
When using the Windows NT standard UPS service
How to set up UPS service
Click
Check Set Check Set
Check Check Check Set Set
Click
7-4 Contact signal
Contact Signal
1. Signal output
Low battery level signal output BL
3. Items that can be set using the contact signal card
Setting the switches
Remote ON/OFF Signal
Output delay time setting for backup signal output BU
Jumper settings
BU/BL signal reverse output setting
Insert/ removal method of contact signal card
4. Contact Signal Connector female DSUB9P
5. Remote ON/OFF connector
6. Contact Signal ratings
7. Contact Signal circuit inside the UPS
8. Example of the use of the Contact Signal circuit
Explanation
9. Precautions and notes for the use of the Contact Signal
Remote ON/OFF circuit
8. Using an SNMP/Web card
8-1 Adding an SNMP/Web card
Description features
8-2 SNMP/Web card outline
Specifications
9. Extending the backup time
9-1 Connecting an additional battery unit
You can connect only one additional battery unit
Adding BUM100S to the BU1002SW
Additional battery connection Additional battery signal connection
Additional battery signal connection
Adding BUM300S to the BU3002SW
BU3002SW BUM300S
Problem
10. Troubleshooting
Check and remedy
A. Specifications
References
BU1002SW
B. Dimensions
BU3002SW
D. Related products
C. Circuit block diagram
BUF1002S for rear fan
OMRON Corporation
K1L-D-06051B