●Setting for whether or not to perform battery test (setting switch 3 )

4.UPS functions

Setting for whether or not to perform battery test (setting switch 3 )

Factory setting: OFF

 

ON

 

 

 

 

 

 

 

 

 

 

DIP

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

2

3

 

4

5

6

 

7

8

OFF: The battery test is automatically executed once every 4 weeks.

ON: Does not perform the auto battery test.

Use this setting to disable Battery Mode for for the regularly performed auto battery test.

Auto startup mode setting (setting switch 4 ) Factory setting: OFF

ON

 

 

 

 

 

 

 

 

 

DIP

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1 2 3 4 5 6 7 8

OFF: (Mode A) After UPS stopped, the UPS is automatically started immediately when “ON” is detected for the AC input.

ON: (Mode B) After UPS stopped, the UPS is automatically started in the AC input’s “OFF to ON” timing that is detected.

(Definition of AC input OFF: When AC input is OFF for 1 second or more)

*Setting switch 4 is valid when the auto startup after recovery from power failure setting (setting switch 2) is set to OFF (auto restart is performed).

*This setting mode is valid only after the UPS has been stopped by the contact signal backup stop signal (BS).

*When a cable is connected to the RS-232C connector and the UPS monitoring software is used, the unit operates in Mode A regardless of this setting.