11 Gas Information

A. Gas Pressure Requirements

Pressure requirements for XLR-AU fireplaces are shown in Table 11.1 below.

Two taps are provided on the right hand side of the gas control for a test gauge connection to measure the inlet and outlet pressures.

The fireplace and its individual shut-off valve must be dis- connected from the gas supply piping system during any pressure testing of the system at test pressures in excess of 6 kPa.

If the fireplace must be isolated from the gas supply pip- ing system by closing an individual shut-off valve, it must be of the handle-less type.

WARNING

Fire Risk

Explosion Risk

High pressure will damage valve.

Disconnect gas supply piping BEFORE pressure testing gas line at test pressures above 6 kPa.

Close the manual shutoff valve BEFORE pressure testing gas line at test pressures equal to or less than 6 kPa.

ON/OFF/REMOTE

SWITCH

GAS VALVE

CONTROL

 

MODULE

DC ADAPTER

Figure 11.1. Valve Components

B. Gas Connection

Note: Have the gas supply line installed in accordance with local building codes by a qualified installer approved and/or licensed as required by the locality.

Note: Before the first firing of the appliance, the gas supply line should be purged of any trapped air.

Note: Consult local building regulations to properly size the gas supply line leading to the (Rp 1/2 in.) hook-up at the unit.

Incoming gas line should be piped into the valve compart- ment and connected to the ISO 7-Rp 1/2 (BSP Rp 1/2) threaded gas inlet connection on the manual shutoff valve.

IMPORTANT NOTICE: (Items 1, 2 and 3 applies to

 

ALL Heat & Glo gas appliances)

 

1.1/2 in. GAS LINE: Run through cavity 70 mm above finished hearth level, NOT RIGID, NOT CLIPPED, with minimum 500 mm into cavity and 120 mm back from plaster face.

2.PVC (COMPOSITE) GASLINE must terminate minimum 500 mm short of gas heater. Copper pipe MUST be the final connection to the gas heater.

3.ISOLATING SWITCH: Location within 1 metre of fireplace, subject to mantelpiece etc. Check to ensure it remains clear of any mantelpiece instal- lation.

Leak test all gas line points and the gas control valve prior to and after starting the gas appliance.

 

Natural Gas

Propane

Butane

 

 

 

 

 

Gas Inlet Pressure

1.13

- 3.40 kPa

2.75 - 3.40 kPa

2.75 - 3.40kPa

Outlet (Manifold) Gas Pressure

.80

- .95 kPa

2.36 - 2.61 kPa

2.36 - 2.61 kPa

Gas Rate

.405 m3/

h

.134 m3/

h

.111 m3/

h

Maximum Gas Consumption

26 MJ/h

26.0 MJ/h

22 MJ/h

Burner Injector

DMS 42 (2.350 mm)

DMS .057 (1.450 mm)

DMS 55 (1.325)

Pilot Injector

 

51

 

30

 

30

 

Columns highlighted in gray = The gas control valve supplied with this product is approved for a maximum inlet pressure of 3.40 kPa. For pressures over 3.40 kPa, an in line pressure regulator must be installed upstream from the gas control valve.

Table 11.1

42

Heat & Glo • XLR-N-AU, XLR-PB-AU2198-906 Rev. M • 5/12

Page 42
Image 42