Internal Relay Output

The inverter has an internal relay output with normally open and normally closed contacts (Type 1 form C). The output signal that controls the relay is configurable; the Alarm Signal is the default setting. Thus, the terminals are labeled [AL0], [AL1], [AL2], as shown to the right. However, you can assign any one of the nine intelligent outputs to the relay. For wiring purposes, the general terminal functions are:

ξ[AL0] – Common contact

ξ[AL1] – Normally open contact

ξ[AL2] – Normally closed contact

Inverter logic circuit board

AL0

AL1

AL2

The relay itself can be configured as “normally open or closed.” Parameter C036, Alarm Relay Active State, is the setting. This setting determines whether or not the relay coil is energized when its output signal is OFF:

ξC036=00 – “Normally open” (relay coil is de-energized when output signal is OFF)

ξC036=01 – “Normally closed” (relay coil is energized when the output signal is OFF)

Since the relay already has normally open [AL1] and normally closed [AL2] contacts, the purpose of the ability to invert the relay coil’s active state may not be obvious. It allows you to determine whether or not an inverter power loss causes the relay to change state. The default relay configuration is the Alarm Signal (C026=05), as shown to the right. And, C036=01 sets the relay to “normally closed” (relay coil normally energized). The reason for this is that a typical system design will require an inverter power loss to assert an alarm signal to external devices.

Inverter logic

AL

circuit board

 

 

 

C026=05

 

 

 

 

 

 

 

 

 

 

 

 

 

C036=01

 

 

 

 

 

 

 

 

AL0

AL1

AL2

 

 

 

 

 

 

 

Relay shown with inverter power ON, Alarm Signal OFF

Monitoring

Operationsand

Monitoring

Operationsand

The relay can be used for other intelligent output signals, such as the Run Signal (set C026=00). For these remaining output signal types, the relay coil typically must NOT change state upon inverter power loss (set C036=00). The figure to the right shows the relay settings for the Run Signal output.

If you assign the relay an output signal other than the Alarm Signal, the inverter can still have an Alarm Signal output. In this case, you can assign it to terminal [11] , providing an open collector output.

Inverter logic

RUN

circuit board

 

C026=00

 

 

C036=00

 

 

AL0

AL1

AL2

Relay shown with inverter power ON, Run Signal OFF

Page 186
Image 186
Hitachi CP-X200 instruction manual -37, Internal Relay Output

CP-X200 specifications

The Hitachi CP-X200 is a versatile and robust projector designed to cater to the needs of educational and business environments. It combines affordability with high-quality performance, making it an attractive option for various presentations and multimedia applications.

At the heart of the CP-X200 is its high brightness capability, with a lumen output of 3,000 ANSI lumens. This feature enables the projector to deliver clear and vibrant images even in well-lit rooms. The resolution of XGA (1024 x 768 pixels) ensures that text and graphics are sharp, making it suitable for everything from classroom lectures to corporate presentations.

One of the standout characteristics of the Hitachi CP-X200 is its advanced lamp technology. The projector uses a long-lasting lamp that can provide up to 5,000 hours of usage in standard mode, allowing for extended intervals between lamp replacements. Additionally, the ECO mode can further enhance the lamp life, extending its longevity while reducing energy consumption.

The CP-X200 is equipped with a variety of connectivity options, including HDMI, VGA, and composite inputs, allowing users to easily connect it to various devices such as laptops, DVD players, and other multimedia systems. The inclusion of USB and RS-232 interfaces ensures compatibility with different control systems, making it a flexible choice for diverse setups.

Another significant feature is the projector's built-in 10-watt speaker, which provides decent audio output, eliminating the need for external speakers in smaller venues. The speaker system enhances presentations, ensuring that audio and visuals are cohesive, promoting better audience engagement.

Portability is another key aspect of the Hitachi CP-X200, which weighs just around 3.5 kg (approximately 7.7 lbs), allowing for easy transport between locations. Its compact design makes it suitable for both fixed installations and mobile use, catering to professionals who require a projector that adapts to various environments.

The user-friendly interface and robust remote control enhance the projector's operability, providing easy access to essential functions. Additionally, features such as auto keystone correction adjust the image to maintain consistent quality even when the projector is not perfectly aligned with the screen.

In summary, the Hitachi CP-X200 is a feature-rich projector that embodies reliability, performance, and ease of use. Its combination of high brightness, various connectivity options, long lamp life, portability, and integrated audio makes it an excellent choice for education and business professionals seeking a dependable presentation solution.