HSV Element Manager Event Codes

Table 8: HSV Element Manager Event Codes: Controller Events (Continued)

Event

Event

Sev-

SWC

Evt.

 

Description

ID

Code

erity

ID

No.

 

3419

88030d5b

3

d

5b

Storage Cell: %1

Event Code: %2 Description: A drive enclosure temperature

 

 

 

 

 

sensor out of range condition has been reported by one of the drive enclosure

 

 

 

 

 

elements. This problem was detected by the Drive Enclosure Environmental

 

 

 

 

 

Monitoring Unit located in the drive enclosure identified in the dencl_num field

 

 

 

 

 

within the rack identified in the rack_num field. The rack_num field will not be

 

 

 

 

 

valid until a future release. The location of the temperature sensor (1 through 11)

 

 

 

 

 

is identified in the alarm_error_code.field.en field as follows: 1 = Power Supply 1

 

 

 

 

 

Exhaust 2 = Power Supply 2 Exhaust 3 = Drive Enclosure Environmental

 

 

 

 

 

Monitoring Unit 4

= Drive Bay 1 5 = Drive Bay 2 6 = Drive Bay 3 7 = Drive

 

 

 

 

 

Bay 4 8 = Drive Bay 5 9 = Drive Bay 6 A = Drive Bay 7 B = Drive Bay 8 C =

 

 

 

 

 

Drive Bay 9 D = Drive Bay 10 E = Drive Bay 11 F = Drive Bay 12 10 = Drive

 

 

 

 

 

Bay 13 11 = Drive Bay 14 The temperature sensor out of range condition is

 

 

 

 

 

described by the content of the alarm_error_code.fie ld.ec field as follows: 1 =

 

 

 

 

 

The element temperature is approaching, but has not reached, the high

 

 

 

 

 

temperature CRITICAL threshold. Continued operation under these conditions

 

 

 

 

 

may result in a CRITICAL condition and may reduce an element’s MTBF. 2 = The

 

 

 

 

 

element temperature is above the high temperature CRITICAL threshold.

 

 

 

 

 

Continued operation under these conditions may result in element failure. 3 =

 

 

 

 

 

The element temperature is approaching, but has not reached, the low

 

 

 

 

 

temperature CRITICAL threshold. Continued operation under these conditions

 

 

 

 

 

may result in a CRITICAL condition and may reduce an element’s MTBF. 4 = The

 

 

 

 

 

element temperature has reached the low temperature CRITICAL threshold.

 

 

 

 

 

Continued operation under these conditions may result in element failure. The

 

 

 

 

 

actual temperature threshold values can be found in the HSV element manager

 

 

 

 

 

GUI.

 

 

 

 

 

 

 

 

3423

88030d5f

6

d

5f

Storage Cell: %1

Event Code: %2 Description: The average temperature of two

 

 

 

 

 

of the three temperature sensor groups (i.e., Drive Enclosure Environmental

 

 

 

 

 

Monitoring Unit, Disk Drives, and Power Supplies) exceeds the CRITICAL level.

 

 

 

 

 

The operational power supply(s) will automatically shut down after a short period

 

 

 

 

 

of time, thereby disabling the drive enclosure. This condition remains active until

 

 

 

 

 

either the problem is corrected, or the operational power supply(s) shut down,

 

 

 

 

 

whichever occurs first. This problem was detected by the Drive Enclosure

 

 

 

 

 

Environmental Monitoring Unit located in the drive enclosure identified in the

 

 

 

 

 

dencl_num field within the rack identified in the rack_num field. The rack_num

 

 

 

 

 

field will not be valid until a future release. Note that in this case the content of

 

 

 

 

 

the alarm_error_code.field.en field is undefined. The actual temperature

 

 

 

 

 

threshold values can be found in the HSV element manager GUI.

 

 

 

 

 

 

 

3439

88030d6f

3

d

6f

Storage Cell: %1

Event Code: %2 Description: An internal Drive Enclosure

 

 

 

 

 

Environmental Monitoring Unit error has occurred. This problem was detected by

 

 

 

 

 

the Drive Enclosure Environmental Monitoring Unit located in the drive enclosure

 

 

 

 

 

identified in the dencl_num field within the rack identified in the rack_num field.

 

 

 

 

 

The rack_num field will not be valid until a future release. The

 

 

 

 

 

alarm_error_code.field.en field contains the value 1 signifying that the Drive

 

 

 

 

 

Enclosure Environmental Monitoring Unit is the affected element. The cause of

 

 

 

 

 

the improper operation is described by the content of the

 

 

 

 

 

alarm_error_code.field.ec field as follows: 1 = An internal Drive Enclosure

 

 

 

 

 

Environmental Monitoring Unit clock error has occurred. 2 = The Inter-IC (I2C)

 

 

 

 

 

bus is not processing data and the Drive Enclosure Environmental Monitoring

 

 

 

 

 

Unit is unable to monitor or report the status of the elements or enclosures. 5 = A

 

 

 

 

 

Backplane NVRAM error has occurred.

 

 

 

 

 

 

 

48