b.Use a flathead screwdriver to the press the release button (1), and then pull the front panel from the bottom to detach the panel (2). The two parts remain connected by a flat cable.
2.Secure the mounting base to the wall using the screws provided.
3.Squeeze the two terminal cover fins to remove the terminal covers.
4.Make the required connections by running the connection cables through the center hole in the bottom of the mounting base and connecting the cables to the terminal block.
5.Separate the connection and control cables from the relay cables.
6.Attach the front panel.
7.Close the associated circuit breaker in the ECS cabinet.
8.Press the power button on the outside of the humidifier to power up the humidifier.
Humidity sensor
The HP POD 20c contains one humidity sensor. It is located in the cold aisle in cooling zone 2.
You need a screwdriver to remove and replace the humidity sensor.