Component to be inspected

Task

Frequency

Capable Party

 

 

 

 

Inspect the door operation and

Annually

Qualified personnel

 

inspect the door gaskets for water

 

 

 

and air leaks.

 

 

Visually inspect the paint. Perform

Annually

Qualified personnel

 

prep and touch-up as necessary.

 

 

Life safety

Component to be inspected

Task

Frequency

Capable Party

 

 

 

 

Manual EPO shunt trip

EPO FUNCTIONAL TEST

Annually

Qualified personnel

 

Manually initiate EPO with the

 

 

 

internal and external push buttons

 

 

 

(if installed) in succession. (Verify

 

 

 

all shunt-trips on all panels trip.)

 

 

Thermal EPO shunt trip

EPO FUNCTIONAL TEST

Annually

Qualified personnel

 

Initiate a thermal (automatic) EPO

 

 

 

shutdown via the EPO

 

 

 

temperature switches located in

 

 

 

the hot aisle. (Verify all shunt-trips

 

 

 

on all panels trip.)

 

 

EPO System Test

EPO NON-FUNCTIONAL TEST

Annually

Qualified personnel

 

Mode Key Switch Test - rotate

 

 

 

keyed switch through all modes.

 

 

 

ARMED MODE - Verify:

 

 

 

Power Indicator - White

 

 

 

Armed Light - White

 

 

 

BYPASS MODE - Verify

 

 

 

Bypass Light - Green

 

 

 

TEST MODE - Verify:

 

 

 

Test Light - Amber

 

 

 

Press EPO button (each in

 

 

 

succession) and thermal trip to

 

 

 

verify:

 

 

 

Reset Light - White

 

 

 

Audible alarm

 

 

 

Visual lamp indicator

 

 

 

Replace light upon failure

 

 

Emergency Lighting

Verify emergency lighting is

Every 2 years

Qualified personnel

 

visible when all lighting is off and

 

 

 

the POD doors are shut.

 

 

Exit signs

Visually inspect Tritium exit signs

Every 2 years

Qualified personnel

 

for operation or damage.

 

 

 

Replace as necessary.

 

 

Emergency egress

Personnel door emergency egress

Bi-annually

Qualified personnel

 

panic bars. (Visual and

 

 

 

operational inspection.)

 

 

Periodic maintenance 67

Page 67
Image 67
HP Performance Optimized Data Center (POD) 20cp manual Life safety, EPO Functional Test