HP Performance Optimized Data Center (POD) 20cp manual Differential pressure sensor

Models: Performance Optimized Data Center (POD) 20cp

1 81
Download 81 pages 57.33 Kb
Page 16
Image 16

4.Remove the control relay module (2).

Replacing the control relay module

1.Align the control relay module with the mounting and power connections.

2.Slide the module until it clicks into the DIN rail.

3.Reconnect all wiring to the control relay module.

Differential pressure sensor

The HP POD 20c uses differential pressure sensing terminals located in the ECS cabinet to take pressure readings from the cold aisle, hot aisle, and cooling fan filters via sensing tubes. The terminal determines cold-to-hot aisle differential pressure and filter differential pressure for all three cooling zones.

You need a small wrench to remove and replace the differential pressure sensor.

Removal and replacement procedures 16