Specifications
General HP POD 20c specifications
Features | Specifications |
|
|
Overall dimensions | • |
| • |
| • |
|
|
Weight1 | • |
| • Maximum fully |
|
|
Maximum power2 | 288 kW |
Power input voltage | 480 V, |
Power input current | 2 x 320 A |
Maximum rack quantity | 10 racks |
Rack Units (RU) per rack | 50 RU |
Rack Units (RU) total | 500 RU |
Average capacity per rack (kW) | 30 kW |
Peak rack capacity | 69 kW |
|
|
Voltage to rack | |
Minimum quantity of PDUs per HP POD 20c | 10 (one per rack) |
Maximum quantity of PDUs per HP POD 20c | 20 (two per rack) |
Maximum power per PDU | 30A = 17 kW; 60A = 34 kW |
Network supported | • Bulk cable |
| • Bulk cable |
| • External rated DEMARC box |
|
|
1The empty weight includes the HP POD 20c structure, empty racks, PDUs, and drop boxes. It does not include IT equipment.
2The maximum power depends on the exact installation and power configuration in your POD. The HP POD 20c is electrically limited to 288 kW.
Electrical specifications
Electrical busway system information
Feature | Specification |
|
|
Number of busways | 2 |
Frequency | 60 Hz |
Amps (per busway) | 200 A |
Voltage (per busway) | |
Grounding | Copper |
Busway configuration |
Specifications 69