HP Performance Optimized Data Center (POD) 20cp manual Temperature sensor cold aisle

Models: Performance Optimized Data Center (POD) 20cp

1 81
Download 81 pages 57.33 Kb
Page 43
Image 43

Temperature sensor (cold aisle)

The HP POD 20c contains three temperature sensors in the cold aisle.

You need a screwdriver and scissors to remove and replace the cold aisle temperature sensor.

Removing the cold aisle temperature sensor

1.Remove the four screws that secure the cold aisle temperature sensor cover (1), and then remove the cover (2).

2.Label the cold aisle temperature sensor wires or take a picture to remember which wires to reconnect later.

3.Disconnect the wires.

4.Remove the two retaining screws, and then remove the cold-aisle temperature sensor housing from the wall.

Replacing the cold aisle temperature sensor

1.Reconnect the wires to the cold-aisle temperature sensor.

2.Reconnect the wires.

3.Re-attach the cold-aisle temperature sensor housing to the wall using the two retaining screws.

Removal and replacement procedures 43

Page 43
Image 43
HP Performance Optimized Data Center (POD) 20cp Temperature sensor cold aisle, Removing the cold aisle temperature sensor