HP Performance Optimized Data Center (POD) 20cp manual Optional features specifications

Models: Performance Optimized Data Center (POD) 20cp

1 81
Download 81 pages 57.33 Kb
Page 71
Image 71

Feature

Specification

 

 

Operating humidity

0% to 100% external

 

10% to 90% non-condensing internal

 

 

Non-operating humidity*

5% to 95% relative non-condensing

 

39ºC (102ºF) maximum wet bulb

 

temperature

 

 

Operating altitude

-76.2 m to 3,048 m (-250 ft to 10,000 ft)

Non-operating altitude

-76.2 m to 9,144 m (-250 ft to 30,000 ft)

*For non-operating specifications, consider the temperature of computer and IT equipment inside the HP POD 20c.

Optional features specifications

Feature

Specification

 

 

Fire suppression

3M Novec 1230 or FM200 fire extinguishing system provided in two canisters (main and

 

reserve)

Card reader

12-key pad with 125 KHz proximity and 13.56 MHz contactless smart card

Humidifier

Provides 0.9-3.63 kg/hr (2-8 lb/hr) of water vapor into cold aisle to maintain POD

 

environment within 20% to 80% relative humidity

 

 

Specifications 71

Page 71
Image 71
HP Performance Optimized Data Center (POD) 20cp manual Optional features specifications