Component to be inspected

Task

Frequency

Capable Party

 

 

 

 

Condensate drain lines and

Inspect and verify that:

Quarterly

Qualified personnel

p-trap

There is no internal blockage

 

 

 

 

 

of the drain line

 

 

 

 

Condensate can freely pass

 

 

 

 

P-traps are intact and not

 

 

 

 

 

leaking

 

 

 

 

There is no blockage of the

 

 

 

 

 

drain line that is external to the

 

 

 

 

 

site drain

 

 

 

 

Clean and clear debris as

 

 

 

 

necessary.

 

 

 

Heat exchanger fans

Inspect and verify that the

Quarterly

Qualified personnel

 

following components are

 

 

 

 

properly secured and operational:

 

 

 

 

Fan

 

 

 

 

Fan mounting

 

 

 

 

Wiring harness

 

 

 

 

Power modules (located in the

 

 

 

 

 

ECS cabinet)

 

 

 

 

 

 

 

 

Chilled water header drain pan

Visually check drains for internal

Monthly, if

Qualified personnel

and lines

and external blockage

 

staffed

 

 

 

 

Quarterly, if

 

 

 

 

 

not staffed

 

 

 

 

 

Conduct an operational check of

Annual

Qualified personnel

 

the external site drain using

 

 

 

 

approximately 5 gallons of water

 

 

 

 

(if possible)

 

 

 

Leak detection

The HP POD 20c includes six heat exchanger condensate sensors. Three sensors are located in the drain pans below each set of heat exchangers, and three sensors are located in the chilled water supply and return header drain pan tray.

Some amount of condensation water can always be expected in the heat exchanger drain pans. If an excessive amount of condensation water accumulates in a drain pan, an alarm is triggered and sent through the HP POD 20c ECS, which indicates a possible leak.

There should be no water in the chilled water supply and return header drain pan. The drain pan should always remain dry.

Leak isolation

WARNING: To reduce the risk of electric shock or damage to the equipment, use extreme caution when removing and replacing components that involve water around the electrical equipment. There is great risk of electrical shock when water is used near electricity.

Periodic maintenance 62