Application Notes – PLCs and Devices

MITSUBISHI FX SERIES PLCS

Registers Accessed

The DN-3000 will only access registers in the Data Register Area of PLC memory (D0 to D9999). When entering register numbers, only the offset into this area (0-9999) should be entered. For example, to access register number D1, the value 1 should be entered. To access register number D9999, the value 9999 should be entered.

RTS Control

The Mitsubishi FX-32 and equivalent PLCs require RTS to be active when sending to the PLC and inactive when receiving from the PLC. The DN-3000 can be configured to do so by performing the following steps when configuring the PLC Port in the DN-3000 Configuration Software:

1)Select “RTS Delay” in the RTS Control selection box

2)Set the RTS Delay time to 2 ms

MODICON PLCS AND MODBUS DEVICES

Registers Accessed

The DN-3000 will only access registers in the Holding Area of PLC memory (40001 to 49999). When entering register numbers, only the offset into this area (1-9999) should be entered. For example, to access register number 40001, the value 1 should be entered. To access register number 49999, the value 9999 should be entered.

OMRON PLCS

Registers Accessed

The DN-3000 will only access registers in the Data Area of PLC memory (DM0 to DM9999). When entering register numbers, only the offset into this area (0-9999) should be entered. For example, to access register number DM1, the value 1 should be entered. To access register number DM9999, the value 9999 should be entered.

PLCs / Protocols Supported

The DN-3000 will communicate with any Omron PLC that uses the Host Link Protocol. On many PLCs, this requires the use of a Host Link Module.

53

Page 59
Image 59
ICP DAS USA DN-3000, DB25, 100-700 PLCS Mitsubishi FX Series Plcs, Modicon Plcs and Modbus Devices, Omron Plcs, RTS Control