Ingersoll-Rand 125-200 HP/90-160 KW Electrical Installation, Hasp Lever TAG KEY Lock, FAN Motor

Models: 125-200 HP/90-160 KW 100-200 HP/75-160 KW

1 93
Download 93 pages 47.56 Kb
Page 15
Image 15

ELECTRICAL INSTALLATION (Continued)

The Intellisys will automatically shut the unit down if the compressor rotation is incorrect, and the display will indicate “CHECK MOTOR ROTATION” and will flash “ALARM”.

For the compressor motor rotation check, the motor jogging time must be as short as possible.

After depressing the start button, IMMEDIATELY depress the “EMERGENCY STOP” button. Should the motor rotation be incorrect, put main disconnect in the OFF position, lock and tag. See Figure 2.4-3.

HASP

LEVER

TAG

KEY

LOCK

FIGURE 2.4-3 MAIN DISCONNECT

LOCKED AND TAGGED

Open the starter box door.

Interchange any two line connections (L1, L2 or L3) at the starter. Close and fasten the starter box door. Recheck for correct rotation.

FAN MOTOR

Observe the compressor cooling fan. The rotation should be in accordance with the fan rotation decal affixed to the fan motor. Cooling air should exhaust through fan end of compressor enclosure.

Should the motor rotation not be correct, put the main disconnect in the OFF position, lock and tag.

Interchange any two fan motor leads at the fan motor manual starter (MMS). Close and fasten the starter box door. Recheck for correct rotation.

Fan motor rotation is clockwise when viewed from the fan motor side.

INTELLISYS OPERATING INSTRUCTIONS

Read and understand the following Intellisys Operating Instructions (See Figure 2.4-4) prior to operating the unit.

NOTE: These instructions are also contained on the decal near the Intellisys panel of the unit.

FIGURE 2.4-4 INTELLISYS

OPERATING INSTRUCTIONS

13

Page 15
Image 15
Ingersoll-Rand 125-200 HP/90-160 KW, 100-200 HP/75-160 KW Electrical Installation, Hasp Lever TAG KEY Lock, FAN Motor