SECOND

After the compressor has started and reached the off-line setting and has unloaded, timer “B” requires the unit to run unloaded for a period of time that the operator can adjust between 2 and 60 minutes.

The setting of timer “B” is part of the options setpoint routine and the timer cancels any accumulated time if the compressor reloads before the timer cycle has finished.

An important point... This unloaded run time may, or may not, be included in the mandatory 10 minute run time used to cool the motor windings.

When the compressor has completed the settings of both timer “A” and timer “B”, the Intellisys controller stops the compressor and displays “STOPPED IN AUTO RESTART.”

Pressure sensor 4APT continues to monitor the package discharge pressure and sends information to the controller which automatically restarts the compressor when the pressure falls to the on-line setting.

An advantage to this method of automatic start/stop control is allowing the compressor to stop much sooner in certain situations and timer settings, thereby reducing power costs.

Some Examples of Operation

EXAMPLE 1

The operator selects an unloaded run time of 2 minutes in the OPTION routine and starts the compressor. The unit runs loaded for 8 minutes, unloads and then runs unloaded for two more minutes.

The total running time is 10 minutes which satisfies timer “A” plus the unit ran two minutes unloaded which also satisfies timer “B,” therefore, the unit stops automatically.

This example shows how timer “B” can sometimes be included within the timer “A” interval. Think of the two timers as running parallel.

EXAMPLE 2

The operator selects an unloaded run time of 3 minutes in the OPTION routine and starts the compressor. The unit runs loaded for 10 minutes and then unloads.

At this point, timer “A” has been satisfied but timer “B” still wants the compressor to run unloaded 3 more minutes before allowing an automatic stop.

The total run time for this example will be 13 minutes.

Remember.... If the unit reloads before timer “B” finishes

the 3 minute setting, the partial time is canceled and timer “B” must restart the 3 minute cycle when the compressor unloads again.

44

Page 46
Image 46
Ingersoll-Rand 100-200 HP/75-160 KW, 125-200 HP/90-160 KW technical manual Second, Some Examples of Operation