EXAMPLE 3

The operator selects an unloaded run time of 10 minutes in the OPTION routine and starts the compressor. The unit runs loaded 12 minutes and then unloads.

After 12 minutes of running, the 10 minute mandatory run-time for timer “A” has been met but the compressor must continue to run unloaded an additional 10 minutes to satisfy timer “B”.

After 10 minutes of unloaded run time, the compressor is stopped automatically and the total run time was 22 minutes.

5.10 REMOTE START/STOP

When starting the compressor from the remote location, the Start button must be held depressed for approximately 2 seconds to activate the remote start function and then released within a maximum of 7 seconds or a Remote Start Failure alarm will occur.

!WARNING

The remote start/stop option allows the operator to control the compressor from a remote mounted start/stop station.

Two different switches can be wired to the controller for remote start/stop. (Refer to Electrical Schematic 8.1 for wiring locations). The switches are customer supplied and must be of momentary type. The stop switch contacts are normally closed and the start switch contacts are normally open.

This machine is remote start and stop equipped.

May start or stop at anytime.

Can cause severe injury or death.

Disconnect power before servicing.

Lock and tag out.

See Operators / Instruction Manual.