3.7 SENSOR CALIBRATION

 

 

 

 

 

 

 

 

 

 

 

 

 

 

-SENSOR CALIBRATION-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0

 

 

 

 

 

 

 

 

 

 

Sensor 1AVPT

 

 

 

 

 

 

P S I

 

 

 

 

CALIBRATE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Sensor 3APT

 

 

 

 

 

 

 

 

 

 

 

 

 

Ready To Start

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CALIBRATE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

STATUS

 

 

 

 

 

 

MAIN MENU

 

 

 

SELECT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Pressure sensor calibration is done through the SENSOR CALIBRATION screen. Sensor calibration can only take place when the machine is stopped. Calibration needs to be done only after a sensor has been replaced or the Intellisys controller has been replaced.

Each of the sensors listed below can be chosen by using the up and down arrow buttons to highlight it on the screen.

Select the highlighted sensor by pressing the SELECT button. Press the CALIBRATE button to start the automatic calibration procedure, or press the CANCEL button to not calibrate it and return to the sensor list.

The calibration screen can be exited by pressing either the STATUS or MAIN MENU buttons. If no buttons are pressed within 30 seconds, the display will return to the CURRENT STATUS screen.

SENSOR CALIBRATION Items

Sensor 1AVPT

Sensor 3APT

Sensor 4APT

Sensor 5CPT

Sensor 6APT

3.8 ALARM HISTORY

 

 

 

 

 

 

 

 

 

 

 

 

 

-ALARM HISTORY-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1 0 0

 

 

 

 

 

 

 

 

 

Alarm History 1

 

 

 

 

P S I

 

 

 

MOTOR OVERLOAD

 

 

 

 

 

 

 

 

 

 

 

 

 

Alarm History 2

 

 

 

 

 

 

 

 

 

 

 

Ready To Start

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

HIGH AIREND DISCH TEMP

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

STATUS

 

 

 

 

 

 

MAIN MENU

 

 

 

SELECT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Alarm History displays each of the Alarm messages for the last 15 Alarms experienced by the machine. It also gives access to displaying the machine operating conditions that existed at the time of each Alarm. The first one shown, “Alarm History 1”, was the most recent Alarm to occur. Note that multiple, consecutive EMERGENCY STOP Alarms are not recorded as separate Alarms, only the first one will be shown.

Each of the last 15 Alarm messages can be seen by moving the Alarm History list up and down using the arrow buttons. Pressing the SELECT button when one of the Alarms is highlighted will display the list of machine values that existed at the time that particular Alarm occurred.

23