Troubleshooting Guide

Precaution in Service or Check

Even after stopping the operation of product, it takes some time to discharge the remaining electricity of the electrolytic capacitor that was charged. Before starting a checking or repairing job, pull out the plug out of the outlet and make sure that the lamp on the control board outdoor unit is off.

The Diagnosis Procedure

Check the supplied voltage to product (AC 220V/230V ± 30V).

Check the connecting cable between Indoor and Outdoor.

Check the blinking number of operation indicator

(refer to the self-diagnosis function).

Check the self-diagnosis table

Indoor

Check the condition of connectors

The condition of P.C.B pattern.

Outdoor

Check the condition of connectors.

The condition of P.C.B pattern.

The electronic components.

68Room Air Conditioner