LG Electronics AS-W096URH1/UBH1/UWH1/UMH1 service manual Heater does not operate at all

Models: AS-W096URH1/UBH1/UWH1/UMH1 AS-W126URH1/UBH1/UWH1/UMH1 AS-W096URH0/UBH0/UWH0/UMH0 AS-W126URH0/UBH0/UWH0/UMH0/UCH0

1 84
Download 84 pages 60.42 Kb
Page 74
Image 74

Troubleshooting Guide

Trouble 6

The heater does not operate at all.

Turn off main power

Check the wire connection of PTC Heater (Refer to Wiring Diagram)

Check the connecting condition of CN-PTC connector on the indor DC P.C.B Ass'y.

Check the soldering condition of CN-PTC connector on the indoor DC P.C.B Ass'y.

Check the Heater driving Circuit.

• Check the pattern between MICOM Pin No. 48 IC02M Pin No. 7 IC02M Pin No. 10 CN-PTC

If there is no problem result of all above check.

Inner side disconnection of PTC Heater unit or restriced operating condition of PTC Heater (pipe temp. is over 45°C, defrosting operation, compressor off, indoor fan off).

74Room Air Conditioner

Page 74
Image 74
LG Electronics AS-W096URH1/UBH1/UWH1/UMH1, AS-W126URH1/UBH1/UWH1/UMH1 service manual Heater does not operate at all