Operation

Protection of theevaporatorpipefromfrosting

If the indoor pipe temperaure is below 0°C in 7 min. after the compressor operates without pause while in cooling cycle operation mode,

compressor, outdoor fan are turned off.

When indoor pipe temp. is 7°C or higher after 2 min pause of compressor

compressor, outdoor fan is turned on according to the condition of the room temperature.

 

 

 

Indoor pipe

 

Comp. free

temp.

6˚C

 

 

7˚C

Comp. Step 4

 

3˚C

 

Comp. Step 2

 

0˚C

 

Comp. off

 

 

 

Protection of the indoorfan from dropletformation (Enclosure sweat and condensed disposaltest)

Control condition : The system operates standard operation without this condition as follows.

Setting temperature <25°C

Indoor fan speed low speed

Outdoor temperature < 30°C

Control method

In operation for 5~20 minutes in , , conditions, return to the previous COMP STEP after operation for 5~40 minutes at the COMP STEP 3.

34Room Air Conditioner

Page 34
Image 34
LG Electronics AS-W096URH1/UBH1/UWH1/UMH1 service manual Protection of the evaporator pipe from frosting, Control method