Portection from overheatingofpowermodule

If the temperature of the heat sink TH. reaches over Toff, the Compressor stop instantly.

It will be limited the compressor operating frequency according to the heat sink TH.(refer to below FIG.)

It will be blink 4 times, when the thermistor is open or short, also the temperature is over Toff.

 

T = (T off - T on)

 

 

Heat Sink Temp.

 

T1 = T on +

T

 

 

 

 

 

 

 

T off ° C

T2 = T on + 2

* T

 

 

 

 

 

 

 

 

 

 

 

 

T2 ° C

 

 

 

 

 

 

 

 

T1 ° C

 

 

 

 

 

 

 

 

T on ° C

 

 

 

 

 

 

 

 

COMP

Free

Fc-1

Fc-2

Fc-1

Fc-2

OFF

Free

Freq.

 

 

 

 

 

 

 

 

No.

MODEL

T on

T off

 

 

 

 

1

AS-W096U_0 Series

85

95

 

 

 

 

2

AS-W126U_0 Series

85

95

 

 

 

 

3

AS-W096U_1 Series

85

95

 

 

 

 

4

AS-W126U_1 Series

85

95

 

 

 

 

Portection from overheatingofcompressor

If the temperature of the discharge pipe of compressor reaches over 130°C or below -30°C the compressor stop instantly.

It will be limited the compressor operating frequency according to the compressor dome TH.(Refer to below Fig.)

Temperature range by COMP SPEC varies by 10°C.

 

D-Pipe Temp.

 

 

T = (T off - T2)/2

 

 

 

 

 

T1 = T2

+ 2

* T

 

 

 

 

 

T3 = T2

+

T

 

COMP Freq. Fh min

Free

Fc-1

Fc-2

OFF

Fc-2

Fc-1

Free

No.

MODEL

T on

T off

 

 

 

 

1

AS-W096U_0 Series

102

110

 

 

 

 

2

AS-W126U_0 Series

88

100

 

 

 

 

3

AS-W096U_1 Series

95

105

 

 

 

 

4

AS-W126U_1 Series

95

105

 

 

 

 