Troubleshooting Guide

Trouble 7

The Outdoor Unit does not operate at all.

Does the Operating LED of indoor unit blink when Operation's ON?

NO

Is the Connection between indoor power relay Pin and terminal block No. 1 right?

YES

Is the connection of cable between indoor and outdoor unit right?

YES

Is the voltage of Terminal Block , in outdoor Control Box about AC220V / 240V?

YES

Is the voltage of NF01J , in outdoor PCB Ass'y about AC220V / 240V when Operation's ON?

YES

Is the Bridge Diode(BD01S) right?

YES

Refer to the self-diagnosis function.

NO

Check the connecting state of connector

NO

Indoor

Outdoor

1(Brown)

1(Brown)

2(Blue)

2(Blue)

3(Green/YL)

3(Green/YL)

4(Red)

4(Red)

 

 

NO

Check the Fuse of Outdoor PCB Ass'y.

NO

Check the PTC and RY-PWR.

NO

Check the Bring Diode.

NO

Replace the PCB Ass'y.

Service Manual 75

Page 75
Image 75
LG Electronics AS-W096URH0/UBH0/UWH0/UMH0, AS-W126URH1/UBH1/UWH1/UMH1 Outdoor Unit does not operate at all, Indoor Outdoor