LG Electronics AS-W096URH1/UBH1/UWH1/UMH1 Pipe Length and the Elevation, Outdoor unit Indoor unit

Models: AS-W096URH1/UBH1/UWH1/UMH1 AS-W126URH1/UBH1/UWH1/UMH1 AS-W096URH0/UBH0/UWH0/UMH0 AS-W126URH0/UBH0/UWH0/UMH0/UCH0

1 84
Download 84 pages 60.42 Kb
Page 58
Image 58

Troubleshooting Guide

PipeLengthandtheElevation

Capacity

Pipe Size

Standard

Max.

Max.

Additional

 

 

Length

Elevation

Length

Refrigerant

(Btu/h)

 

 

GAS

LIQUID

(m)

B (m)

A (m)

(g/m)

 

 

 

 

 

 

 

 

7k~14k

3/8"(Ø9.52)

1/4"(Ø6.35)

4 or 7.5

7

15

20

 

 

 

 

 

 

1/2"(Ø12.7)

1/4"(Ø6.35)

4 or 7.5

7

15

20

 

 

 

 

 

 

 

 

 

1/2"(Ø12.7)

1/4"(Ø6.35)

4 or 7.5

15

30

20

 

 

 

 

 

 

 

18k~28k

5/8"(Ø15.88)

1/4"(Ø6.35)

4 or 7.5

15

30

20

 

 

 

 

 

 

 

 

5/8"(Ø15.88)

3/8"(Ø9.52)

4 or 7.5

15

30

30

 

 

 

 

 

 

 

30k~38k

5/8"(Ø15.88)

3/8"(Ø9.52)

7.5

15

30

30

 

 

 

 

 

 

3/4"(Ø19.05)

3/8"(Ø9.52)

7.5

15

30

50

 

 

 

 

 

 

 

 

Outdoor unit

A

Indoor unit

B

Outdoor unit

Oil trap

A

 

Indoor unit

B

In case more than 5m

CAUTION:* Capicity is based on standard length and maximum allowance length is the basis of reliability.

* Oil trap should be installed per 5~7 meters.

58Room Air Conditioner

Page 58
Image 58
LG Electronics AS-W096URH1/UBH1/UWH1/UMH1 Pipe Length and the Elevation, Oil trap should be installed per 5~7 meters