Installation

PipingLengthandElevation

Capacity

 

Pipe Size

Standard

Max.

Max.

Additional

(Btu/h)

GAS

 

LIQUID

Length (m)

Elevation B (m)

Length A (m)

Refrigerant (g/m)

 

 

 

 

 

 

 

 

9k

3/8"

 

1/4"

4 or 5

7

15

20

 

 

 

 

 

 

 

 

12k

1/2"

 

1/4"

4 or 5

7

15

20

 

 

 

 

 

 

 

 

Indoor unit

B

A

Outdoor unit

A

Indoor unit

Outdoor unit

Outdoor unit

 

Oil trap

A

 

 

B

Indoor unit

 

B

If piping length is more than 5m

CAUTION: Capacity is based on standard length and maximum allowance length is on the basis of reliability.

Oil trap should be installed every 5~7 meters.

FixingInstallationPlate

The wall you select should be strong and solid enough to prevent vibration

1.Mount the installation plate on the wall with

type "A" screws. If mounting the unit on a concrete

wall, use anchor bolts.

Mount the installation plate horizontally by aligning the centerline using a level.

Installation Plate

Type "A" screw

2.Measure the wall and mark the centerline. It is also important to use caution concerning the location of the installation plate-routing of the wiring to power outlets is through the walls typically. Drilling the hole through the wall for piping connections must be done safely.

CHASSIS

 

Distance (mm)

 

(Grade)

 

 

 

 

A

B

C

D

 

 

 

 

 

 

SU

92

44

67

44

(9k~12k)

 

 

 

 

 

 

 

 

 

(SU)

 

C

Installation plate

D

B

Ø70mm

A

Ø70mm

Left rear piping

Right rear piping

14Room Air Conditioner

Page 14
Image 14
LG Electronics AS-W096URH1/UBH1/UWH1/UMH1 service manual Piping Length and Elevation, Fixing Installation Plate