Lincoln Electric SVM136-A Controls And Settings, Operation, FIGURE B.1 - CASE FRONT CONTROLS

Models: SVM136-A

1 102
Download 102 pages 56.21 Kb
Page 19
Image 19
CONTROLS AND SETTINGS

Return to Section TOC

Return to Section TOC

Return to Master TOC

Return to Master TOC

B-5

B-5

OPERATION

CONTROLS AND SETTINGS

All operator controls and settings are located on the case front assembly. See Figure B.1 for their locations.

FIGURE B.1 – CASE FRONT CONTROLS

 

 

8

9

10

11

 

 

 

 

 

1

 

 

 

 

 

2

7

6

5

 

4

3

1. POWER SOURCE PILOT LIGHT

6. DC AMMETER

2. ON/OFF POWER TOGGLE SWITCH

7. AUXILIARY POWER CONNECTIONS FOR WIRE FEEDER AND

3. OUTPUT CONTROL POTENTIOMETER

OTHER EQUIPMENT (115V AND 42V)

4. OUTPUT CONTROL SWITCH (WITH LOCAL OR

8. VOLTMETER "+" ELECTRODE OR "-" ELECTRODE SWITCH

REMOTE POSITIONS)

9. THERMAL PROTECTION INDICATOR LIGHT

5. DC VOLTMETER

 

Return to Section TOC

Return to Section TOC

Return to Master TOC

Return to Master TOC

1.POWER SOURCE PILOT LIGHT: This light indi- cates that the power source input contactor is ener- gized (closed). This also means that the main power transformer and all auxiliary control transformers are energized.

2.ON/OFF POWER TOGGLE SWITCH: Energizes or deengergizes the input contactor. The switch turns the machine ON or OFF. Position "I" is ON; position "0" is OFF.

3.OUTPUT CONTROL POTENTIOMETER: Controls output voltage.

4.OUTPUT CONTROL SWITCH (WITH LOCAL OR REMOTE POSITIONS): Selects the mode of control. In the "Local" position, control is by the machine con- trol panel. In the "Remote" position, control is by either a wire feeder unit or through an optional remote control device.

5.DC VOLTMETER (OPTIONAL): Displays actual out- put voltage.

6.DC AMMETER (OPTIONAL): Displays actual output current.

7.AUXILIARY POWER AND REMOTE CONTROL CONNECTIONS FOR WIRE FEEDER AND OTHER EQUIPMENT (115V AND 42V): The 14-pin amphe- nol receptacle provides either 115 or 42 VAC as well as remote control connections. Terminal strips with screw connections are located behind the hinged control panel for hard wired control. A strain relief connector is provided for cable entry. The 42 VAC auxiliary is not available at the terminal strip.

8.VOLTMETER "+" ELECTRODE OR "-" ELEC- TRODE SWITCH: Selects the electrode polarity for the remote work sensing lead (#21) when using automatic or semiautomatic wire feeders. It must agree with the actual electrode polarity chosen and with the wire feeder polarity switch on the feeder.

9.THERMAL PROTECTON INDICATOR LIGHT: This light indicates that either of the two protective ther- mostats has opened. Welding output is disabled but input power is still applied.

10.42 VAC AUXILIARY CIRCUIT BREAKER: This 10 amp breaker protects the 42 VAC auxiliary circuit.

11.115 VAC AUXILIARY CIRCUIT BREAKER: This 10 amp breaker protects the 115 VAC auxiliary circuit.

IDEALARC CV-400

Page 19
Image 19
Lincoln Electric SVM136-A service manual Controls And Settings, Operation, Return to Section TOC Return to Section TOC