| DC rack cabling 37 | |
|
|
|
| Junction | Junction |
|
|
|
| box #4 | box #4 |
Length | #10 AWG | #8 AWG | #6 AWG | AWG | AWG |
|
|
|
|
|
|
no | no | no | no | yes | |
|
|
|
|
|
|
Over 210 m (700 ft) | no | no | no | no | no |
|
|
|
|
|
|
Notes: |
|
|
|
|
|
1.
The cabinet and module ground wire specification is #10 AWG insulated green safety ground wire.
2.
The cabinet conduit can be 19.1 mm
Metric wire conversion
| Industry standard | Resistance at 20 C |
AWG No. | nominal (sq mm) | (Ohm/100 m) |
|
|
|
2 | 35 | 0.05 |
|
|
|
4 | 25 | 0.08 |
|
|
|
6 | 16 | 0.13 |
|
|
|
8 | 10 | 0.20 |
|
|
|
10 | 6 | 0.33 |
|
|
|
12 | 4 | 0.63 |
|
|
|
14 | 2.5 | 1.00 |
|
|
|
16 | 1.5 | 1.40 |
|
|
|
18 | 1 | 2.00 |
|
|
|
20 | 0.75 | 2.90 |
|
|
|
22 | 0.5 | 4.60 |
|
|
|
DC rack cabling
The following photograph shows typical rack power cabling:
Nortel CallPilot
1002rp Server Hardware Installation
5.0 23 February 2007
Copyright © 2007, Nortel Networks | Nortel Networks Confidential |