No. | Parameter | Notes |
|
|
|
Segment Parameters - Program 3
1300 | Run Program (value = Delayed Start value) | Write only | |
|
|
| |
1301 | No. of Cycles Programmed | 1 to 9999 plus 10000 (INF) | |
|
|
|
|
1302 | Timebase | 0 | = hours/mnutes, 1 = minutes/seconds |
|
|
|
|
1303 | Guaranteed Soak Band value | 0 | (OFF), 1 to span |
|
|
| |
1304 | Final Setpoint values | Segment 1 at address 1304 | |
to | (Soak = |
| |
1319 |
| Segment 16 at address 1319 | |
|
|
| |
1320 | Rate values (Soak = | Segment 1 at address 1320 | |
to |
| ||
1335 |
| Segment 16 at address 1335 | |
|
|
| |
1336 | Time values | Segment 1 at address 1336 | |
to |
|
| |
1351 |
| Segment 16 at address 1351 | |
|
|
| |
1352 | Event Marker settings | Bit 0 = Event 16 Bit 15 = Event 1 | |
|
|
|
|
Segment Parameters - Program 4
1400 | Run Program (value = Delayed Start value) | Write only |
|
|
|
1401 | No. of Cycles Programmed | 1 to 9999 plus 10000 (INF) |
|
|
|
1402 | Timebase | 0 = hours/minutes, 1 = |
|
| minutes/seconds |
|
|
|
1403 | Guaranteed Soak Band value | 0 (OFF), 1 to span |
|
|
|
1404 | Final Setpoint values | Segment 1 at address 1404 |
to | (Soak = | |
1419 |
| Segment 16 at address 1419 |
|
|
|
1420 | Rate values (Soak = | Segment 1 at address 1420 |
to | ||
1435 |
| Segment 16 at address 1435 |
|
|
|
1436 | Time values | Segment 1 at address 1436 |
to |
| |
1451 |
| Segment 16 at address 1451 |
|
|
|
Some of the parameters which do not apply to a particular instrument configuration (e.g. PB2 on a single output instrument) will accept reads & writes. Others will accept reads only, and will return an exception if an attempt is made to write values to them. The values read will in all cases be undefined. It is the user’s responsibility to make sure that values read reflect a possible state of the instrument.