Omega CN1166 manual Linear Inputs, Remote Run/Hold Input, Relay Outputs, SSR Drive Outputs

Models: CN1166

1 88
Download 88 pages 37.01 Kb
Page 10
Image 10

1.3.5Linear Inputs

For linear mA input ranges, connection is made to Terminals 4 and 6 in the polarity shown in Figure 1-4. For linear mV and V ranges, connection is made to Terminals 4 and 5 in the polarity shown in Figure 1-4. For details of the linear input ranges available, refer to Appendix A.

1.3.6Remote Run/Hold Input

With this option fitted, Terminals 11 and 12 are used for external Run/Hold control of the currently-selected program; this has an effect identical to that of the front panel RUN key. These terminals may be connected to (a) the voltage-free contacts of a switch or relay, or (b) a TTL-compatible voltage. This is an edge-sensitive input for which the following convention has been adopted:

For TTL input, OFF = logic 1 and ON = logic 0

For a voltage-free input, OFF = open and ON = closed

Program control is as follows:

 

OFF-ON transition:

The currently-selected program will run (or

 

will resume running if it is currently held).

ON-OFF transition:

The currently-running program will be

 

held.

NOTE: When this input is used, the front panel RUN key can be used only to abort a program. Powering-up the Profile Controller whilst this input is ON will not cause a program to run. The RS485 Serial Communications option and the Remote Run/Hold option are mutually exclusive.

1.3.7Relay Outputs

The contacts are rated at 2A resistive at 120/240V AC.

1.3.8SSR Drive Outputs

These outputs produce a time-proportioned non-isolated DC signal (0 - 4.2V nominal into 1k￿ minimum).

1.3.9Solid State Outputs

These outputs provide up to 1A AC drive with a longer lifetime than an electromechanical relay. For further details, refer to Appendix A.

S077-1

Volume I

1-5

Page 10
Image 10
Omega CN1166 manual Linear Inputs, Remote Run/Hold Input, Relay Outputs, SSR Drive Outputs, Solid State Outputs