Omega CN1166 manual Remote Run/Hold Input Option

Models: CN1166

1 88
Download 88 pages 37.01 Kb
Page 68
Image 68

(mV) input, alarms operate as if the

Input Range

Displayed Code

Input Range

Displayed Code

 

 

 

 

0 - 20mA

3413

0 - 5V

4445

4 - 20mA *

3414

1 - 5V

4434

0 - 50mV

4443

0 - 10V *

4446

10 - 50mV

4499

2 - 10V

4450

 

 

 

 

* Default

process variable has gone over-range.

DC Linear: Ranges Selectable from Front Panel:

(Changes may also be required to the CPU PCB link jumpers - see Volume I Subsection 2.5.1.)

Scale Range Maximum:

–1999 to 9999.

Decimal point as required.

Scale Range Minimum:

–1999 to 9999.

Decimal point as for Scale

 

Range Maximum.

Minimum Span:

1 display LSD.

 

Sensor Break Protection:

Applicable to 4 - 20mA, 1 - 5V and 2 - 10V

 

ranges only. Break detected within two

seconds. Control outputs set to OFF (0% power); Alarms operate as if the process variable has gone under-range.

REMOTE RUN/HOLD INPUT (OPTION)

Type:

Voltage-free or TTL-compatible;

 

edge-sensitive.

 

OFF-ON transition - currently-selected

 

program will run or (if currently held)

 

resume running.

 

ON-OFF transition - currently-running

 

program will be held.

Voltage-Free Operation:

Connection to contacts of external switch

 

or relay; contacts open = OFF (minimum

 

contact resistance = 5000￿), contacts

 

closed = ON (maximum contact resistance

 

= 50￿).

TTL levels:

OFF: –0.6V to 0.8V

 

ON: 2.0V to 24V

A-3

Volume II

S077-A

Page 68