Omega CN1166 manual Parameter, Function, Adjustment Range, Default, value

Models: CN1166

1 88
Download 88 pages 37.01 Kb
Page 40
Image 40

Parameter

Function

Adjustment Range

Default

value

 

 

 

 

 

 

 

ON/OFF

Switching differential for one output or

0.1% to 10.0% of

0.5%

Differential

both outputs set to ON/OFF control

input span

 

 

(PB1, PB2 or both = 0) - see Figure

 

 

 

2-1.

 

 

 

 

 

 

Setpoint Lock

Enables/disables setpoint (SP)

OFF - SP adjustable

OFF

 

adjustment in Base Mode.

ON - SP not

 

 

 

adjustable

 

 

 

 

 

Recorder Output

Process variable or setpoint value (as

￿1999 to 9999

Input

Scale Maximum

applicable) for which the recorder

(decimal point

Range

 

output is a maximum

position as for input

Maximum

 

 

range)

 

 

 

 

 

Recorder Output

Process variable or setpoint value (as

￿1999 to 9999

Input

Scale Minimum

applicable) for which the recorder

(decimal point

Range

 

output is a minimum

position as for input

Minimum

 

 

range)

 

 

 

 

 

Output 1 Power

Limits Output 1 power level (to protect

0% to 100% of full

100%

Limit

the process)

power

 

 

 

 

 

Output 1 Cycle

Limits the frequency of operation of

0.5, 1, 2, 4, 8, 16, 32,

32 secs.

Time

output relay to maximise relay life

64, 128, 256 or 512

 

 

 

secs.

 

 

 

 

 

Output 2 Cycle

Limits the frequency of operation of

0.5, 1, 2, 4, 8, 16, 32,

32 secs.

Time

output relay to maximise relay life

64, 128, 256 or 512

 

 

 

secs.

 

 

 

 

 

Process High

If Alarm 1 is a Process High Alarm, the

Input Range Minimum

Input

Alarm 1

value of the process variable at or

to Input Range

Range

 

above which Alarm 1 will be active (see

Maximum

Maximum

 

Figure 2-2)

 

 

 

 

 

 

Process Low

If Alarm 1 is a Process Low Alarm, the

Input Range Minimum

Input

Alarm 1

value of the process variable at or

to Input Range

Range

 

below which Alarm 1 will be active (see

Maximum

Minimum

 

Figure 2-2)

 

 

 

 

 

 

Band Alarm 1

If Alarm 1 is a Band Alarm, the band of

0 to input span from

5 units

 

process variable values, centred on the

(program) setpoint

 

 

(program) setpoint, outside which the

 

 

 

process variable will cause this alarm to

 

 

 

be active (see Figure 2-2)

 

 

 

 

 

 

Deviation

If Alarm 1 is a Deviation Alarm, gives a

￿input span from

5 units

Alarm 1

value above (positive value) or below

(program) setpoint

 

 

(negative value) the (program) setpoint.

 

 

 

If the process variable deviates from

 

 

 

the setpoint by a margin greater than

 

 

 

this value, the alarm becomes active

 

 

 

(see Figure 2-2)

 

 

 

 

 

 

Alarm 1

Defines a hysteresis band on the “safe”

1 to 250 units

1 unit

Hysteresis

side of the Alarm 1 value

 

 

 

 

 

 

 

 

 

 