Parameter | Function | Adjustment Range | Default | |
value | ||||
|
|
| ||
|
|
|
| |
ON/OFF | Switching differential for one output or | 0.1% to 10.0% of | 0.5% | |
Differential | both outputs set to ON/OFF control | input span |
| |
| (PB1, PB2 or both = 0) - see Figure |
|
| |
|
|
| ||
|
|
|
| |
Setpoint Lock | Enables/disables setpoint (SP) | OFF - SP adjustable | OFF | |
| adjustment in Base Mode. | ON - SP not |
| |
|
| adjustable |
| |
|
|
|
| |
Recorder Output | Process variable or setpoint value (as | 1999 to 9999 | Input | |
Scale Maximum | applicable) for which the recorder | (decimal point | Range | |
| output is a maximum | position as for input | Maximum | |
|
| range) |
| |
|
|
|
| |
Recorder Output | Process variable or setpoint value (as | 1999 to 9999 | Input | |
Scale Minimum | applicable) for which the recorder | (decimal point | Range | |
| output is a minimum | position as for input | Minimum | |
|
| range) |
| |
|
|
|
| |
Output 1 Power | Limits Output 1 power level (to protect | 0% to 100% of full | 100% | |
Limit | the process) | power |
| |
|
|
|
| |
Output 1 Cycle | Limits the frequency of operation of | 0.5, 1, 2, 4, 8, 16, 32, | 32 secs. | |
Time | output relay to maximise relay life | 64, 128, 256 or 512 |
| |
|
| secs. |
| |
|
|
|
| |
Output 2 Cycle | Limits the frequency of operation of | 0.5, 1, 2, 4, 8, 16, 32, | 32 secs. | |
Time | output relay to maximise relay life | 64, 128, 256 or 512 |
| |
|
| secs. |
| |
|
|
|
| |
Process High | If Alarm 1 is a Process High Alarm, the | Input Range Minimum | Input | |
Alarm 1 | value of the process variable at or | to Input Range | Range | |
| above which Alarm 1 will be active (see | Maximum | Maximum | |
| Figure |
|
| |
|
|
|
| |
Process Low | If Alarm 1 is a Process Low Alarm, the | Input Range Minimum | Input | |
Alarm 1 | value of the process variable at or | to Input Range | Range | |
| below which Alarm 1 will be active (see | Maximum | Minimum | |
| Figure |
|
| |
|
|
|
| |
Band Alarm 1 | If Alarm 1 is a Band Alarm, the band of | 0 to input span from | 5 units | |
| process variable values, centred on the | (program) setpoint |
| |
| (program) setpoint, outside which the |
|
| |
| process variable will cause this alarm to |
|
| |
| be active (see Figure |
|
| |
|
|
|
| |
Deviation | If Alarm 1 is a Deviation Alarm, gives a | input span from | 5 units | |
Alarm 1 | value above (positive value) or below | (program) setpoint |
| |
| (negative value) the (program) setpoint. |
|
| |
| If the process variable deviates from |
|
| |
| the setpoint by a margin greater than |
|
| |
| this value, the alarm becomes active |
|
| |
| (see Figure |
|
| |
|
|
|
| |
Alarm 1 | Defines a hysteresis band on the “safe” | 1 to 250 units | 1 unit | |
Hysteresis | side of the Alarm 1 value |
|
| |
|
|
|
| |
|
|
|
|
Volume II |