NetScan User’s Manual Configuring and Starting NetScan 1-5
If you observe a configuration error, perform an error status query (see E? in Appendix A). If you observe
any other type of error condition, make note of the error and contact your service representative.
Error Condition LED Indicators
ALARM TRIGGER SCAN ERROR POWER
General Hardware Failure ON ON -Flash- ON
ROM Invalid for U22, COMM2 -Flash- ON
ROM Checksum Error for
U21 Comm1 ON -Flash- ON
ROM Checksum Error for
U22 COMM2 ON -Flash- ON
Non-Volatile RAM Error ON -Flash- ON
Dynamic RAM Error ON ON -Flash- ON
Interprocessor COM Error ON ON ON -Flash- ON
Configuration Error ON ON
If no problems are found NetScan will begin its power-up initialization. This self-test is performed each
time the unit is powered up regardless of whether power-on was caused by the power switch or the Power-
On Reset (*R) command.
During initialization, NetScan self test performs the following steps:
• Checks for errors at power-up.
• Checks the flag in the NV-RAM to determine if it should power-up with factory default
settings or a user-defined configuration.
• Loads appropriate registers with corresponding values in NV-RAM.
• Checks a flag to see if alarms should be enabled at power-up, and if so, enables them.
• Loads channel configuration registers.
• Loads program sequencer with appropriate channel configurations.
• Resets computations processor to begin acquiri ng sc ans.
The self-test takes approximately 5 seconds to complete; after which, NetScan is ready for normal
operation.
Install Software/Configure Address Settings for Ethernet OperationBe sure you have completed the hardware-related steps on page 1-4 prior to performing
the steps below. Failure to complete the hardware-related steps will result in a
communications error.
Use Microsoft Windows Run dialog box to configure NetScan’s address and install the ChartView program
group. Direct Windows to run the SETUP.EXE file found on Installation Diskette 1. Follow the on-screen
dialog boxes to complete a successful installation.
Early in the setup you will be prompted to enter your Network Interface ID Number. This number appears
on your Network Registration Sheet and must be entered to enable ChartViewNET.
Screen Prompt for Entering the Network Interface Registration ID