3. Timer Remote Controller (RCS-TM80BG)

Use AWG#20 to AWG#16 wires.

Remote controller wiring can be extended to a maximum of 1640 ft.

(1)Strip the insulation to approximately 35/64" from the ends of the wires that will be connected.

(2)Twist together the 2 wires and create a crimp connection at the wire joint.

(3)If a special crimping tool is not used, or if the connection is soldered, insulate the wires using insulation tape.

5. Group Control Using 2 Remote Controllers

It does not matter which of the 2 remote controllers you set as the main controller. When using multiple remote controllers (up to 2 can be used), one serves as the main remote controller and the other as the sub-remote controller.

Provided wire joint (white)

Remote controller wiring

Power wire from remote controller unit

Fig. 2-2

Remote controller

(main)(sub)

 

 

 

 

Connection wiring 1 2

 

1

2

 

 

 

 

 

 

 

for group control

 

 

 

 

2P terminal

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

base for remote

 

 

 

 

 

 

 

 

 

 

 

 

control wiring

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

2

 

 

 

 

1

2

 

 

 

 

1

2

 

 

 

Indoor unit

 

 

Indoor unit

 

 

Indoor unit

 

 

 

No. 1

 

 

 

No. 2

 

 

 

No. 3

 

 

 

 

 

Wire joint

1 2

Indoor unit

No. 8

: Ground (earth)

Fig. 2-3

6. Remote Controller Setting Mode

To set the remote controller main/sub setting or change the sensor, follow the steps below.

 

 

Press both

and

buttons on the remote controller for more than

 

 

 

 

4 seconds together.

 

 

 

 

 

Select CODE No. with

buttons.

CODE

ITEM

 

DATA

ITEM

 

 

Change DATA with

(TIMER) buttons.

 

 

 

 

 

 

 

 

RCU. Main/Sub

Sub

Main

Press

. Finally, press

.

 

 

Clock display

24 hours

12 hours (AM/PM)

* DATA is memorized in the RCU. (DATA setting will not be changed even

 

 

RCU. CK

RCU. CK

Normal

when the power is turned off.)

 

Room temperature sensor

Main unit

RCU

*Make sure to set [Normal] for RCU. CK.

7.Indoor Unit Setting Mode

1

1

2

2

3

3

To select the ventilation setting or change the temperature unit, follow the steps below.

Press

+

+

buttons on the remote controller for more than 4 sec-

 

onds together.

 

 

 

CODE

Select CODE No. with

buttons.

ITEM

Change DATA with

 

(TIMER) buttons.

 

 

Press

. Finally, press

.

 

*DATA is memorized in the indoor unit. (DATA setting will not be changed even when the power is turned off.)

 

DATA

No

 

Yes

oC

 

oF

4

4

8. To Display the Sensor Temperature:

Press both and buttons on the remote controller for more than 4 seconds together.

Change the sensor address (CODE No.) with buttons.

Select the UNIT No. which you want to call with the button. Press the button to fi nish service mode.

9. To Display the Trouble History:

Press both and buttons on the remote controller for more than 4 seconds together.

Change the alarm message: buttons Press the button to fi nish service mode.

2-19

5

5

6

6

7

7

8

8

Page 39
Image 39
Sanyo KHX1852, UHX2452 Group Control Using 2 Remote Controllers, Remote Controller Setting Mode, Indoor Unit Setting Mode