Trouble Diagnosis

1. Contents of Remote Controller Switch Alarm Display

 

 

ON:

Blinking:

 

 

 

 

 

 

OFF:

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Wired

 

 

 

 

 

 

 

Wireless

 

 

 

 

 

 

 

 

remote

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

remote controller

 

 

 

 

control

 

 

 

 

 

 

 

receiver display

 

Possible cause of malfunction

 

display

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Operation

 

 

 

 

Timer

Standby for heating

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Thermistor

Outdoor unit

Compressor 1 (INV) discharge temp. sensor

 

F04

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

fault

 

Compressor 2 (constant speed) discharge temp. sensor

 

F05

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Compressor 3 (constant speed) discharge temp. sensor

 

F22

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Outdoor air temp. sensor

 

F08

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Heat exchanger 1 liquid temp. sensor

 

F07

 

 

 

 

Operating and

timer

 

 

Heat exchanger 1 gas temp. sensor

 

F06

 

 

 

lamps blinking

 

 

 

 

 

 

 

 

 

 

alternately

 

 

 

 

 

 

Compressor intake temp. sensor (suction temp)

 

F12

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

High-pressure sensor

 

F16

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Low-pressure sensor

 

F17

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Heat exchanger 2 liquid temp. sensor

 

F24

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Heat exchanger 2 gas temp. sensor

 

F23

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Ceiling panel connection failure

 

 

<<P09>>

 

 

 

Timer and heat

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Protective

Indoor unit

Thermal protector in indoor unit fan motor is activated.

 

<<P01>>

 

 

 

ready lamp blinking

device

 

Float switch is activated.

 

<<P10>>

 

 

 

alternately

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Fan inverter protection function activated.

 

<<P12>>

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

O2 sensor activated

 

P14

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Outdoor unit

Compressor 1 (INV) discharge temp. trouble

 

P03

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

High-pressure switch

 

P04

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Reverse phase (missing phase) detected.

 

P05

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DCCT, ACCT overcurrent (compressor less than 80 Hz)

 

P16

 

 

 

 

Operating and heat

 

 

Compressor 2 (constant speed) discharge temp. trouble

 

P17

 

 

 

 

 

 

 

 

 

 

ready lamp blinking

 

 

Compressor 3 (constant speed) discharge temp. trouble

 

P18

 

 

 

alternately

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Outdoor unit fan trouble

 

P22

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DCCT, ACCT overcurrent (80 Hz or more)

 

P26

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Start failure caused by compressor wire missing phase, DCCT

 

P29

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

failure, or similar problem (INV compressor start failure).

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Failure of nonvolatile memory IC (EEPROM) on indoor unit control PCB

 

 

 

 

Operating and

timer

 

 

 

 

lamp blinking

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

F29

 

 

simultaneously

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Failure of nonvolatile memory IC (EEPROM) on outdoor unit control PCB

 

 

 

 

Operating and

timer

 

 

 

 

 

 

 

lamp blinking

 

 

 

 

 

 

 

 

F31

 

 

simultaneously

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Protective

Overload current detected.

Compressor 2 (constant speed)

 

H11

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Compressor 3 (constant speed)

 

H21

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

device

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Lock current detected.

Compressor 2 (constant speed)

 

H12

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Compressor 3 (constant speed)

 

H22

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

No current detected when

Compressor 1 (INV)

 

H03

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

compressor was ON.

Compressor 2 (constant speed)

 

H13

 

 

 

Timer lamp blinking

 

 

Compressor 3 (constant speed)

 

H23

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Discharge temp. sensor

Compressor 2 (constant speed)

 

H15

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

trouble

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Compressor 3 (constant speed)

 

H25

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Outdoor unit protection

Low-pressure trouble

 

H06

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Outdoor unit protection

HIC trouble alarm

 

H31

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Connection failure of oil detection sensor

Compressor 1 (INV)

 

H08

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Compressor 2 (constant speed)

 

H27

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Compressor 3 (constant speed)

 

H28

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Fusing of electromagnetic contact (Current detected when compressor was OFF)

 

only blinking

 

(No display changes)

Automatic backup operation

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

<< >> alarm indication: Does not affect the operation of other indoor units.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

<> alarm indication: In some cases may affect the operation of other indoor units.

3-3