Service Checker

1. Outdoor Unit Maintenance Remote Controller

4. Monitoring Operations

Display the indoor unit and outdoor unit sensor temperatures.

<Operating procedure>

Press and hold the (CHECK) and (CANCEL) buttons simultaneously for 4 seconds or longer to engage temperature monitor mode.

During temperature monitoring, illuminates.

(The display and operations are the same as for monitor mode using the indoor unit remote controller.)

Press the (UNIT) button and select the indoor unit to monitor.

Press the temperature setting and buttons and select the item code of the temperature to monitor.

The unit No. of the selected indoor unit, and the temperature data, are displayed.

To end monitoring, press the (CHECK) button.

4

1

2

3

The display returns to the normal display.

NOTE The display does not blink.

Display of unit No. 1 (main unit)

DN

Description

 

Remarks

 

Intake temp.

 

 

 

 

 

 

 

E1

 

 

 

 

 

 

 

E2

 

 

 

 

 

 

 

E3

 

Indoor unit

 

 

 

 

 

Discharge temp.

 

 

 

 

 

 

 

Discharge temp. setting

 

 

 

 

 

 

 

Indoor unit electronic control valve position

STEP

 

 

 

 

 

 

Discharge temp. 1 at Compressor 1

 

 

 

 

 

 

 

Discharge temp. 2 at Compressor 2

 

 

 

 

 

 

 

High-pressure sensor temp.

 

 

 

 

 

 

 

Heat exchanger gas 1

 

 

 

 

 

 

 

Heat exchanger liquid 1

 

 

 

 

 

 

 

Heat exchanger gas 2

 

 

 

 

 

 

 

Heat exchanger liquid 2

 

 

 

 

 

 

 

Outdoor air temp.

 

 

 

 

 

 

 

Not used

 

 

 

 

 

 

 

Inverter primary current

A

 

 

 

 

 

 

Current at Compressor 2 (CT2)

A

Outdoor unit

 

 

 

 

 

MOV1 pulse

STEP

 

 

 

 

 

 

MOV2 pulse

STEP

 

 

 

 

 

 

Discharge temp. 3 at Compressor 3

 

 

 

 

 

 

 

Current at Compressor 3 (CT3)

A

 

 

 

 

 

 

MOV3 pulse

STEP

 

 

 

 

 

 

Heat exchanger gas 3

 

 

Heat exchanger liquid 3

Low-pressure sensor temp.

Suction temp.

Oil 1

Oil 2

Oil 3

Actual operating frequency

Hz

NOTE

0A and subsequent items are outdoor unit data. 0A – 22 are for unit No. 1.

2A – 42 are for unit No. 2. 4A – 62 are for unit No. 3. 62 – 89 are for unit No. 4.

 

 

6-7

1

2

3

4

5

6

7

8

Page 109
Image 109
Sanyo AHX0752, UHX2452, UHX0752, UHX1252 Monitoring Operations, Display of unit No main unit, Indoor unit, Outdoor unit