PCB and Functions

2. Indoor Unit Control PCB

6. Explanation of Functions (CR-KXRP56AN, CR-KXRP80AN, POW-KRP50A)

T10

6P fl ag (yellow): Used for remote control.

 

(CN105)

Control items:

Start/stop input

Remote controller prohibit input

(for remote control)

 

Start signal output

Alarm signal output

 

 

EXCT

2P plug (red): Can be used for demand control. When input is present, forces the unit to

(CN009)

operate with the thermostat OFF.

 

zExamples of wiring

*Lead wire with 2P plug (special-order part: WIRE K/854 05280 75300)

Relay (field supply)

EXCT

Relay coil signal

(2P plug (red))

 

 

Indoor unit control PCB

 

Note: The length of the wiring from the indoor unit control PCB to the relay must be 6-9/16 ft.

 

or less.

 

 

DISP

2P plug (white): Short-circuiting this plug allows the unit to be operated by the remote

(CN010)

controller, even if it is not connected to an outdoor unit. (In this case, alarm "E04," which

 

indicates trouble in the serial communication between the indoor and outdoor unit, does not

 

occur.)

 

 

CHK

2P plug (white): Test pin. Short circuiting this plug allows the operation of the indoor fan

(CN011)

motor (high) and fl ap motor (F1 position) to be checked.However this test operation stops

 

if the indoor unit protection mechanism is activated. The unit can be operated even if the

 

remote controller and outdoor unit are not connected. However even if the remote controller

 

cannot be connected, it cannot be used to operate the unit. This function can be used for

 

short-term tests.

 

 

JP001

Jumper wire: Allows selection of the T10 terminal start/stop signal. Status at shipment: Pulse

 

signal. Jumper wire cut: Static signal (continuous signal)

 

 

FAN DRIVE

2P plug (white): This terminal sends a signal to the ventilation fan when the FAN button on

(CN017)

the wired remote controller is used to operate a commercially-available ventilation fan.Use a

 

ventilation fan that can accept no-voltage A contact as the external input signal.

zExamples of wiring

*Lead wire with 2P plug (special-order part: WIRE K/854 05280 50600)

 

DC 12V

Relay (field supply)

FAN DRIVE

 

 

To external-control input

(2P plug

 

 

terminal on ventilation fan

(white))

 

 

 

Indoor unit control PCB

Note: The length of the wiring from the indoor unit control PCB to the relay must be 6-9/16 ft. or less.

4-11

1

2

3

4

5

6

7

8