Sanyo XHX1852, UHX2452, UHX0752, UHX1252, UHX3652, UHX1852, THX2452 List of Simple Setting Items

Models: DHX4852 XHX1852 KHX2452 KHX0752 XHX2452 THX1852 UHX3652 UHX1852 KHX1252 KHX0952 THX2452 AHX0752 DHX3652 XHX1252 UHX1252 UHX0752 KHX1852 THX1252 UHX2452 AHX1252 AHX0952 XHX3652

1 114
Download 114 pages 30.48 Kb
Page 52
Image 52

Remote Control Functions

3. Timer Remote Controller (RCS-TM80BG)

List of Simple Setting Items

1

1

2

2

3

3

4

4

5

5

6

6

7

7

8

8

 

0000

Not displayed

 

0001

150 hours

 

 

 

Filter sign ON time

0002

2,500 hours

(filter lifetime)

0003

5,000 hours

 

 

 

 

 

0004

10,000 hours

 

 

 

 

0005

Use the filter clogging sensor.

 

 

 

 

0000

Standard (setting at time of shipping)

Degree of filter fouling

 

 

0001

Highly fouled

 

(Filter sign ON time is reduced to one-half the set time.)

 

 

 

0001

Central control address 1

 

 

 

 

0002

Central control address 2

 

 

 

Central control address

0003

Central control address 3

 

 

 

 

 

0064

Central control address 64

 

 

0099

No central control address set (setting at time of shipping)

 

 

 

 

 

Operating mode

0000

Normal (setting at time of shipping)

 

priority change

0001

Priority

 

 

 

 

 

 

 

 

Compressor ON

 

Compressor OFF

 

 

 

 

 

 

0000

MED 1 min., LO 3 min.

 

LO

 

 

 

 

 

Fan speed when

0001

MED

 

LO

 

 

 

 

heating thermostat is

0002

LO

 

LO

OFF

 

 

 

 

0004

MED 1 min., LO 3 min.

 

MED

 

 

 

 

 

 

 

 

0005

MED

 

MED

 

 

 

 

 

 

0006

LO

 

MED

 

 

 

 

 

 

0000

No shift

 

 

 

 

 

0001

Shifts intake temperature 2°F (1°C) down.

 

 

 

Heating intake

0002

Shifts intake temperature 4°F (2°C) down.

 

 

 

 

0003

Shifts intake temperature 6°F (3°C) down.

temperature shift

 

 

 

 

0004

Shifts intake temperature 8°F (4°C) down.

 

 

 

 

 

0005

Shifts intake temperature 10°F (5°C) down.

 

 

 

 

0006

Shifts intake temperature 12°F (6°C) down.

 

 

 

 

Electric heater

0000

No heater

 

installation

0001

Heater installed

 

 

 

 

 

 

 

Humidifying when

0000

No (setting at time of shipping)

 

heater thermostat is

 

 

 

 

0001

Yes

 

OFF

 

 

 

 

 

Change to remote

0000

Thermostat OFF differential: –2°F (– 1°C) (setting at time of shipping)

controller sensor

 

 

 

 

0001

Thermostat OFF differential: –1°F (– 0.5°C)

thermostat differential

 

 

 

 

Mode

0000

Normal

 

dependency

0001

 

 

 

 

 

 

 

 

 

 

 

Cooling-only

0000

Normal

 

 

 

 

 

0001

Cooling only

 

 

 

2-32

Page 52